Masonry or Prefabricated Chimney Conversion
The GF 300 DV is approved for use with Simpson Dura- vent Chimney Kit #934 in a masonry chimney or a prefabricated solid fuel listed chimney.
These installation requirements must be followed:
1.Use the guidelines for Coaxial Vent Termination appropriate for your gas type on pages 11 - 12.
2.In masonry chimney, a fireclay liner or listed steel liner, must be present the entire length of the chim- ney.
3.Chimney height should not exceed 35 ft. (10.67 m).
4.The liner must have an inside dimension of 6” round or greater. (USE KIT #934)
5.Prefabricated chimneys must be UL 103 or ULC
Exhaust
Gas
Cap Adaptor-
included in
#934 Kit
4” Flex Pipe not included in kit
Support/Wall
Thimble Cover -
included
in#934 Kit
#991 Vertical
Termination Cap
Intake Air
Use Standard
Simpson
Pipe from
stove to
thimble
IMPORTANT NOTICE
THE USE OF AN EXISTING CHIMNEY AS AN AIR INTAKE IS NOT COVERED UNDER THE ANSI
SULTING ITS/WHI PRODUCT CERTIFI- CATION. THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PROCEEDING WITH THIS INSTALLATION METHOD.
Figure 16. Vent System through a masonry chimney using the Simpson
13