Pressurized Combustion Chamber System Operational Checklist

1.Manifold gasket properly sealed.

2.Viewport not damaged or cracked.

3.Combustion chamber free of debris and undamaged.

4.Manifold component block properly installed.

5.No leaks at manifold connection.

6.Manifold door screws securely tightened.

TROUBLESHOOTING CHART

PROBLEM

 

POSSIBLE CAUSE(S)

 

CORRECTIVE ACTION

 

1.

Transformer unplugged.

1. Plug transformer back into 120 VAC. outlet.

NO HOT WATER

2.

No power at outlet.

2.

Repair service to outlet.

3.

Thermostat defective.

3.

Replace Thermostat.

 

 

4.

Air Intake Chamber Fan defective.

4.

Replace Air Intake Chamber Fan Assembly.

 

5.

Pressure Switch defective.

5.

Replace Pressure Switch Assembly.

 

6.

Gas Valve/Thermostat Switch in “OFF

6.

Move Gas Valve/Thermostat Switch to “ON POSI-

 

 

POSITION”.

 

TION”.

 

 

 

 

1. Thermostat set too low.

1. Set temperature control higher.

INSUFFICIENT HOT WATER

2.

Thermostat defective.

2.

Replace thermostat.

3.

Heater undersized.

3.

Reduce hot water use.

 

4.

Low gas pressure.

4.

Contact dealer.

 

5.

Incoming water is unusually cold.

5.

Allow more time for heater to reheat.

 

6.

Leaking hot water pipes or fixtures.

6.

Have plumber check and repair leaks.

 

 

 

 

 

1.

Low gas pressure.

1. Check with gas utility company.

 

2.

Improper calibration.

2.

Replace thermostat.

 

3.

Thermostat set too low.

3.

Turn temperature dial to desired setting.

SLOW HOT WATER

4.

Water heater too small.

4.

Install adequate heater.

RECOVERY

5.

Wrong piping connections.

5.

Correct piping-dip tube must be in cold inlet.

 

6.

Wasted hot water.

6.

Advise customer.

 

 

 

 

WATER TOO HOT

1.

Thermostat set too high.

1. Set temperature control lower.

 

 

 

 

see, “WATER TEMPERATURE REGULATION”,

 

 

 

 

section.

 

 

 

 

1. Dirt in burner ports.

1. Turn off heater and gas, clean burner head.

 

2.

Combustion air path restricted.

2.

Check intake venting arrangements for obstruc-

BURNER FLAME

3.

Not enough dilution air for proper com-

3.

tions.

Check intake venting arrangements for obsruc-

YELLOW - LAZY

4.

bustion.

4.

tions.

 

Main burner line clogged.

Clean, locate source and correct.

 

5.

Obstruction in main burner orifice.

5.

Clean or replace orifice.

 

6.

Burner flame too high.

6.

Check orifice and replace if necessary.

 

7. Flame burns at orifice/thermostat not

7.

Replace thermostat

 

8.

functioning properly.

8.

Check with gas utility company.

 

Low gas pressure.

 

 

 

 

 

1. Orifice too large/wrong orifice.

1.

Replace with correct-orifice.

BURNER FLAME FLOATS

2.

High gas pressure.

2.

Check with gas utility company.

3.

Water heater flue or vent system

3.

Clean flue and burner-locate source and correct.

AND LIFTS OFF PORTS

 

blocked.

 

 

 

4.

4.

Locate source and correct.

 

Cold drafts.

 

 

 

 

 

1.

Insufficient secondary air.

1. Provide ventilation to water heater. Check

COMBUSTION ODORS

 

 

 

flue.

2.

Water heater flue or vent system

2.

Clean, locate source and correct.

 

 

3.

blocked.

3.

Provide fresh air ventilation.

 

Heater installed in a confined area.

 

 

 

 

 

36

Page 36
Image 36
Kenmore 153.33264, 153.33262 manual Pressurized Combustion Chamber System Operational Checklist, Troubleshooting Chart

153.33262, 153.33264 specifications

The Kenmore 153.33262 and 153.33264 are highly versatile and efficient portable air conditioners designed to provide optimal cooling solutions for indoor spaces. These models stand out in their class due to their advanced features, technologies, and user-friendly characteristics, making them suitable for a variety of environments, from small apartments to large rooms.

One of the primary features of both the Kenmore 153.33262 and 153.33264 is their high cooling capacity. With powerful BTUs, they can effectively cool spaces up to a specified square footage. This capability ensures that users can maintain a comfortable indoor climate even during the hottest summer months. Their energy efficiency is another notable aspect, allowing homeowners to enjoy cooler air without incurring exorbitant energy bills.

The two models are equipped with various modes of operation, including cooling, fan, and dehumidifying modes. This multifunctionality allows users to customize their comfort based on prevailing weather conditions. For instance, the dehumidifying mode effectively reduces excess moisture in the air, creating a more comfortable environment, particularly in humid regions.

Both air conditioners come with a user-friendly digital interface that features an easy-to-read LED display. The interface allows for straightforward adjustments to the temperature, fan speed, and operating modes. Furthermore, remote control functionality enhances convenience, enabling users to change settings from across the room.

In terms of technology, these models incorporate a self-evaporating system that minimizes the need for manual water drainage. This feature is particularly advantageous for users who prefer low-maintenance options. Additionally, both units feature a washable air filter, designed to capture dust and allergens, improving air quality and ensuring that the units operate efficiently.

Portability is another significant characteristic of the Kenmore 153.33262 and 153.33264. Built-in caster wheels and side handles allow for easy movement from room to room, making them ideal for temporary cooling needs. The easy installation process and included window exhaust kit mean users can set up the units quickly without requiring professional assistance.

In conclusion, the Kenmore 153.33262 and 153.33264 portable air conditioners offer a robust combination of high cooling performance, energy efficiency, and user-friendly features. Their advanced technologies and versatile functionalities make them an ideal choice for those seeking effective indoor air conditioning solutions.