TROUBLESHOOTING FLOWCHART

TROUBLESHOOTING FLOWCHART

APPLY POWER TO

APPLIANCE

REQUEST NO FOR HEAT PRESENT?

YES

 

 

 

 

 

 

 

 

 

IS

NO

WAIT FOR PRESSURE

PRESSURE SWITCH

SWITCH TO OPEN

PROVEN OPEN WITHIN

 

 

 

DISPLAY ERROR

 

 

 

5 SECONDS?

 

 

 

NUMBER 7

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMBUSTION

 

 

 

 

 

FAN ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IS

 

 

 

 

 

PRESSURE SWITCH

NO

WAIT FOR PRESSURE

PROVEN CLOSED

 

 

 

SWITCH TO CLOSE

 

 

 

DISPLAY ERROR

WITHIN 11

 

 

 

 

 

 

NUMBER 6

SECONDS?

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ISNO

PRESSURE SWITCH

PROVEN OPEN WITHIN

5SECONDS?

YES

3 MINUTE

AUTOMATIC RESET

TIME DELAY

WAIT FOR PRESSURE

SWITCH TO OPEN

DISPLAY ERROR

NUMBER 7

ONE HOUR

AUTOMATIC RESTART

TIME DELAY

PREPURGE

COMBUSTION FAN

OFF

IS

NO

TURN OFF

COMBUSTION FAN,

IGNITOR

 

 

 

DISPLAY ERROR CODE

 

 

 

OKAY?

 

 

 

NUMBER 8

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IGNITOR ON FOR

 

 

 

 

WARM-UP TIME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TURN OFF

 

 

COMBUSTION FAN

COMBUSTION

 

AFTER POST-PURGE

FAN OFF

 

DISPLAY ERROR 3

GAS VALVE OPENS

COMBUSTION FAN

ON

MAIN

BURNER LIGHTS NO

LESS

YES

YES

WAIT FOR PRESSURE

 

NO

 

IS

SWITCH TO CLOSE

 

 

 

PRESSURE SWITCH

 

 

 

PROVEN CLOSED

DISPLAY ERROR

 

 

 

 

 

 

WITHIN 5

NUMBER 6

 

 

 

 

 

 

SECONDS?

 

 

 

 

 

 

 

AND IS SENSED DURING TRIAL FOR

IGNITION

GAS VALVE CLOSES

THAN 3 TRIES FOR IGNITION?

INTERPURGE

YES

IGNITOR TURNS OFF

ISYES

FLAME SENSE LOST?

NO

GAS VALVE CLOSES

NO

 

 

LOST

YES

 

LESS THAN 4

 

 

 

 

TIMES?

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

IS

NO

WAIT FOR PRESSURE

 

 

PRESSURE SWITCH

 

 

PROVEN CLOSED

 

 

 

SWITCH TO CLOSE

 

 

 

 

 

DISPLAY ERROR

 

 

WITHIN 5

 

 

 

 

 

 

 

 

NUMBER 6

 

 

SECONDS?

 

 

 

 

 

YES

 

 

 

 

 

 

IS

YES

 

 

 

REQUEST FOR HEAT

 

 

 

GAS VALVE OFF

 

NO

 

 

 

 

SATISFIED?

 

 

 

 

 

 

Please Note:

 

The control continually monitors

 

internal circuits and external sensors.

 

Error codes noted above, and those for

COMBUSTION FAN

self-diagnostic faults can be found on

OFF AFTER POST-

pages 38 through 40.

PURGE DELAY