Kenmore 153.33264 manual Closed System/Thermal Expansion, Temperature and Pressure Relief Valve

Models: 153.33262 153.33264

1 44
Download 44 pages 10.06 Kb
Page 22
Image 22
Closed System/Thermal Expansion
Pressure Reducing Valve with Bypass
Main Water Supply

Hot Water Outlet

Metal Drain

Pan 1-3/4”

Depth Max.

In a closed system use a thermal expansion tank

Cold Water

Inlet Valve

Cold Water SupplyTemperature and Pressure Relief Valve to Fixture

Temperature and Pressure (T&P)

Manual background Relief Valve (Optional Top T&P

Relief Valve Not Shown)

Massachusetts: Install a vacuum relief in cold water line per section 19 MGL 142

Discharge line

(Do Not Cap or Plug)

1“ Min.

Drain line 3/4”

ID Min.

 

Drain

6“ Min.

Closed System/Thermal Expansion

As water is heated, it expands (thermal expansion). In a closed system, the volume of water will grow. As the volume of water grows, there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent temperature-pressure relief valve operation: water discharged from the valve due to excessive pressure build

Typical water piping installation

FIGURE 23.

Manual background Mixed Water

To Fixtures

Unmixed

Hot Water

Manual background Cold Water

Inlet

Hot Water

Outlet

Mixing Valve

(Set To 1200 F)

Follow The Mixing Valve

Manufacturer’s Instructions

FIGURE 24.

Please note the following:

up. The temperature-pressure relief valve is not intended for the constant relief of thermal expansion. This condition is not covered under the limited warranty.

A properly-sized thermal expansion tank should be installed on all closed systems to control the harmful effects of thermal expansion. Contact a plumbing service agency or your retail supplier regarding the installation of a thermal expansion tank.

Temperature and Pressure Relief Valve

Explosion Hazard

Temperature-pressure relief valve must comply with ANSI Z21.22-CSA 4.4 and ASME code.

• Properly sized temperature- pressure relief valve must be installed in opening provided.

• Can result in overheating and excessive tank pressure.

• Can cause serious injury or death.

• The system should be installed only with piping that is suitable

for potable (drinkable) water such as copper, CPVC, or

polybutylene. This water heater must not be installed using

iron piping or PVC water piping.

• Use only pumps, valves, or fittings that are compatible with

potable water.

• It is recommend that only full flow ball or gate valves are used

in water piping installations. The use of valves that may cause

excessive restriction to water flow is not recommended.

• Use only 95/5 tin-antimony or other equivalent solder. Any

lead based solder must not be used.

• Piping that has been treated with chromates, boiler seal, or

other chemicals must not be used.

Metal Drain Pan

Temperature and

Pressure Relief Valve

(T&P)

Discharge line 3/4” Min.

Do not cap or plug.

Manual background 6” Max.

Manual background Drain

• Chemicals that may contaminate the potable water supply

must not be added to the piping system.

FIGURE 25.

22

Page 22
Image 22
Kenmore 153.33264, 153.33262 manual Closed System/Thermal Expansion, Temperature and Pressure Relief Valve, Explosion Hazard