Kidde C3010-D manual Operating and Alarm Characteristics, A steady display of

Models: C3010 C3010-D

1 19
Download 19 pages 25.63 Kb
Page 15
Image 15
A steady display of

6.Model C3010-D (with digital display) Operating Characteristics

The following table illustrates the possible digital displays, describes the audible alarm patterns, and the recommended actions to take.

Operating and Alarm Characteristics

LCD Display Shows

Alarm Sound

Unit Status

Recommendation

 

 

 

 

 

 

A steady display of

4 quick beeps,

Alarm condition.

Refer to “What to

 

 

CO concentration

5 secs. silence,

Dangerous

do When the Alarm

 

from 30-999. Red

repeating

concentrations of

Sounds” (inside front

LED flashes with beep

 

CO detected

cover)

 

 

 

 

 

 

Brief “888” for

None

Self test when first

None – CO has

 

 

approximately 30

 

powered up

not been detected.

 

seconds

 

 

Numbers shown for

 

 

 

 

test purpose only

 

 

 

 

 

 

“- - -” followed

4 quick beeps,

Test/Reset button is

None – CO has

 

 

by “888” are

5 seconds

pressed

not been detected.

 

shown to indicate

silence,

 

Numbers shown for

test mode

repeated once

 

test purpose only

 

 

 

 

 

Steady “0” displayed, None

Normal DC

None

 

 

dot flashing every 5

 

operation with

 

 

seconds, Green LED

 

good batteries

 

 

flashes every 30 secs.

 

(sensing no CO)

 

 

“Lb” flashes

One quick beep

 

alternately with

every 60 seconds

 

any number,

 

 

 

Amber LED flashes every

 

second.

 

Unit batteries are not capable of powering the unit either because of age, storage or the voltage of the battery

If unit is cold, allow to warm up above 68°F. If the unit is at room temperature and is beeping /flashing every 60 seconds the unit needs to be replaced.

 

“Err” displayed,

One quick beep

Unit is Error

 

Amber LED flashes

every 30 seconds

condition

 

every second and

 

 

 

 

 

green LED flashes error code

 

 

every other 30 second period.

 

 

 

Display is blank

Constant alarm

Unit malfunction

 

 

 

 

 

Press and hold the test button for 5 seconds to perform a reset. If unit continues to beep or alarm, using a screwdriver slide the switch on the back of the unit up to the shut down position. Unit will not respond to CO.

Number from

None

Peak Level Memory

Refer to following

11-999 displayed.

 

activated. Highest

section for informa-

 

 

concentration of

tion regarding Peak

 

 

CO detected is

Level Memory

 

 

displayed

 

Manual background “End” displayed.Green Manual backgroundManual backgroundManual backgroundManual backgroundManual background LED flashes error code every other 30 second period and amber LED flashes every second.

Two quick

End of unit life

Replace unit imme-

beeps every

 

diately. Unit will not

30 seconds

 

respond to CO.

The problems listed above are under normal operating conditions. Other “Err” conditions could exist. If you should have any questions regarding display conditions, call our Consumer Hotline.

Page 15
Image 15