WIRES ON ALARM HARNESS | CONNECTED TO |
Black | Hot Side of AC Line |
White | Neutral Side of AC Line |
Red | Interconnect Lines (Red Wires) of |
| Other Units in the Multiple |
| Station Set up |
BATTERY INSTALLATION
See Maintenance (section 6) for battery installation
CAUTION! IF BATTERY REMINDER FINGER IS NOT HELD DOWN IN THE BATTERY COMPARTMENT BY THE BATTERY, THE BATTERY DOOR WILL NOT CLOSE, THE AC QUICK CONNECTOR WILL NOT ATTACH TO THE ALARM, AND THE ALARM WILL NOT ATTACH TO THE TRIM RING (SEE SECTION 6, FIGURE 8).
MOUNTING INSTRUCTIONS
CAUTION: THIS UNIT IS SEALED. THE COVER IS NOT REMOVABLE!
1.Remove the trim ring from the back of the alarm by holding the trim ring and twisting the alarm in the direction indicated by the “OFF” arrow on the alarm cover.
2.After selecting the proper smoke alarm location as described in section 1 and wiring the AC QUICK CONNECT harness as described in the WIRING INSTRUCTIONS, attach the trim ring to the electrical box (see figure 6).
3.Pull the AC QUICK CONNECTOR through the center hole in the trim ring and mount the ring, making sure that the mounting screws are positioned in the small ends of the keyholes before tightening the screws.
4.Plug the AC QUICK CONNECTOR into the back of the alarm (see figure 5), making sure that the locks on the connector snap into place. Then push the excess wire back into the electrical box through the hole in the center of the trim ring.
5.If you have finished all the WIRING, BATTERY INSTALLATION AND TRIM RING MOUNTING STEPS, you can install the alarm on the trim ring. Note: The alarm will mount to the trim ring in 4 positions (every 90 degrees).