For vented models:
Vent system requirements
Do not terminate the vent system in an attic or other enclosed area.
Do not use 4" (10.2 cm) laundry- type wall caps.
Use metal vent only. Rigid metal vent is recommended. Do not use plastic or metal foil vent.
Flexible vent is not recommended. Flexible vent creates back pressure that greatly reduces the hood's performance.
• The size of the vent should be |
uniform. |
• Use no more than three 90° |
elbows. |
• Make sure there is a minimum |
of 24" (61 cm) of straight vent |
between the elbows if more |
than one elbow is used. |
• Do Not install two elbows |
together. |
• The length of vent system and |
number of elbows should be |
kept to a minimum to provide |
efficient performance. |
• The vent system must have a |
damper. If roof or wall cap has |
a damper, Do Not use damper |
supplied with the range hood. |
• Use duct tape to seal all joints |
in the vent system. |
(8.3 cm x 25 cm) vent through the wall
wall cap
Wall venting
Recommended vent system length
Use 3 1/4" x 10" (8.3 cm x 25 cm) vent with maximum length of
26 feet (8 m) for vent system. For best performance, use no more than three 90° elbows. To calculate the length of system you need, add the equivalent feet (meters) for each vent piece used in the system. See the following example.
vent system
|
|
|
| wall | |||||||||
(8.3 cm x 25 cm) |
|
|
|
| |||||||||
|
|
|
| cap | |||||||||
90° elbow |
|
|
|
| |||||||||
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| 6 ft. (1.8 m) |
|
|
| |||
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
| 3 ft. |
|
|
|
|
|
| ||||
|
| (0.93 m) |
|
|
|
|
|
| |||||
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Maximum length | = 26 ft. (8 m) | ||||||||||||
1 — 90° elbow | = |
| 5 ft. | (1.5 m) | |||||||||
9 ft. (2.8 m) straight | = |
| 9 ft. | (2.8 m) | |||||||||
1 — wall cap | = |
| 0 ft. | (0 m) | |||||||||
Length of |
|
|
|
|
| ||||||||
(8.3 cm x 25 cm) |
|
|
|
|
| ||||||||
system | = 14 ft. | (4.3 m) |
Recommended standard fittings
(8.3 cm x 25 cm) 90° elbow
= 5 ft. (1.5 m)
(8.3 cm x 25 cm) flat elbow
= 12 ft. (3.7 m)
(8.3 cm x 25 cm) wall cap
= 0 ft. (0 m)
• Use caulking to seal exterior wall |
or roof opening around the cap. |
Note: It is recommended that the vent system be installed before installing the hood.
Product dimensions
Note: Underside of hood must be a minimum of 24" (61 cm) from cooking surface.
Venting methods
Vent system needed for installation is not included.
(8.3 cm x 25 cm) vent through the roof
Roof venting
(8.1 cm)
(34.0 cm)
(12.1 cm)
(6.5 cm)
(3.0 cm)
(12.9 cm)
(45.1 cm)
(25.2 cm)
(4.0 cm)
(19.6 cm)
| |
| (4.4 cm) |
Do not | |
(4.6 cm) | |
| use these |
knockouts | |
(25.0 cm) |
|
30" (76.2 cm) 36" (91.4 cm)
3