7
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Mantel
Floor Protection
Combustible Wall
6”
(152mm)
9-1/2”
(241mm)
7-1/2”
(191mm)
10”
(254mm)
Max.
6”
(152mm)
23-3/8”
(594mm)
3”
(76mm)
1-1/2”
(38mm)
The floor protector must be a non-combustible material extending beneath the insert from the surround panels forward and to the front and sides as shown in Figure 7. Important, if anything other than a masonry hearth is used in the installation you must use the Heat Kit (Cat. No. 79024).Minimum Size Floor Protection
Outline of Insert Base
Zero Clearance Kit and Heat Kit Installation The Winslow™ PI40 insert has a Zero Clearance Kit (Cat. No. 79025) and a Heat Kit (Cat. No. 79024) approved for new construction or remodel installations. See Zero Clearance and Heat kit installation instructions at the back of this manual for requirements. Both kits have been tested and approved through OMNI Testing Laboratories Inc.
6”
(152mm)
6”
(152mm) 3”
(76mm)
3”
(76mm)
6”
(152mm)
Insert Base
Firebox Front Edge
Floor Protection
31-3/4”
(807mm)
7-7/16”
(189mm)
19-1/4”
(489mm)
6-11/16”
(170mm)
6-11/16”
(170mm)
18-3/8”
(467mm)
Hearth Protection(shaded gray)Figure 6Figure 7Figure 8CLEARANCES TO COMBUSTIBLES

INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT

MANUFACTURER.

Important: The control board attaches to the back of the right side surround panel. Therefore, the width of the fireplace firebox needs to be 36” (914 mm) wide at the front if the insert with control board is to slide into the firebox. Extended surround panels are available to accommodate narrower fireboxes. IMPORTANT

• Minimum clearances specified may not allow

for ease of operation and maintenance (please

take this in to account when planning the instal-

lation).

• Recommended clearance zone from the front

of the appliance to combustibles is 4 feet mini-

mum.

• Clearances to combustibles for the appliance

can only be reduced by means approved by the

regulatory authority.

HEARTH PROTECTION