Lennox International Inc 15GCSX Table Gas Heat Application Data, Table Gas Pipe Capacity−FT3 / HR

Models: Gas Packaged Units 15GCSX

1 24
Download 24 pages 47.47 Kb
Page 10
Image 10
Do not loosen compressor mounting bolts.

Compressors

Units are shipped with the compressor mountings factory−adjusted and ready for operation.

CAUTION

Do not loosen compressor mounting bolts.

Gas Supply and Piping

Check the unit rating plate to confirm whether unit is equipped for use with natural gas or LP/propane. If conversion is required use the approved conversion kit.

NOTE − Units are shipped equipped for natural gas, but can be converted to LP/propane with a conversion kit. Conversion must be performed by an approved licensed pipe fitter or technician.

All LP/propane gas equipment must conform to the safety standards of the National Fire Protection Association. Complete information regarding tank sizing for vaporization, recommended regulator settings, and pipe sizing is available from most regulator manufacturers and LP/propane gas suppliers.

Proper sizing of gas piping depends on the cubic feet per hour of gas flow required, specific gravity of the gas and length of run. In the United States, the current National Fuel Gas Code Z223.1 should be followed in all cases unless superseded by local codes or gas company requirements. Refer to tables 2 and 3. In Canada, refer to the current CSA B.149 installation codes.

Table 2

Gas Heat Application Data

Unit

Input Rating

Output Rating

Gas Capacity*

Heating Size

(Btu)

(Btu)

(FT3 / HR)

 

 

 

 

68

67,500

54,000

63

 

 

 

 

83

82,500

66,000

77

 

 

 

 

90

90,000

72,000

84

 

 

 

 

110

110,000

88,000

102

 

 

 

 

138

137,500

110,000

128

 

 

 

 

*Based on 1075 Btu per cubic foot of natural gas.

Before connecting piping, check with gas company or authorities having jurisdiction for local codes or requirements. When installing gas supply piping, length of run from gas meter must be considered in determining pipe size for 0.5 inch w.c. maximum pressure drop. Do not use supply pipe smaller than unit

gas connection. For natural gas unit, supply pressure at the unit gas connection must be a minimum of 5 inches w.c. and a maximum of 10.5 w.c. For LP/propane gas units, supply pressure at the unit gas connection must be a minimum of 11 inches w.c. and a maximum of 13.0 inches w.c.

Table 3

Gas Pipe Capacity−FT3 / HR

 

Nominal Iron Pipe Size (inches)

Length in Feet

 

 

 

 

 

1/2 in.

3/4 in.

1 in.

1−1/4 in.

 

 

 

 

 

 

 

 

 

 

10

132

278

520

1050

 

 

 

 

 

20

92

190

350

730

 

 

 

 

 

30

73

152

285

590

 

 

 

 

 

40

63

130

245

500

 

 

 

 

 

50

56

115

215

440

 

 

 

 

 

60

50

105

195

400

 

 

 

 

 

70

46

96

180

370

 

 

 

 

 

80

43

90

170

350

 

 

 

 

 

90

40

84

160

320

 

 

 

 

 

100

38

79

150

305

 

 

 

 

 

The gas supply piping should be routed through the grommet on the side of the unit. Refer to figure 7.

Gas Piping and Electrical Conduit Access

Gas Line Entry Table 2Table 3

Thermostat Gas Piping and Electrical Conduit AccessManual background

Entry

Line Voltage

Entry

Figure 7

When making piping connections, a drip leg should be installed on vertical runs to serve as a trap for sediment or condensate. A 1/8 inch N.P.T. tap accessible for test gauge connection must be provided in field piping upstream from gas supply connection to unit. Install a ground joint union between gas control manifold and the manual main shut−off valve. See figure 8.

Compounds used on threaded joints of gas piping shall be resistant to the action of propane/LP gases.

Page 10

Page 10
Image 10
Lennox International Inc 15GCSX, Gas Packaged Units Table Gas Heat Application Data, Table Gas Pipe Capacity−FT3 / HR