Lennox International Inc Gas Packaged Units, 15GCSX Cool, Heat, Continuous Fan, Dehumidification

Models: Gas Packaged Units 15GCSX

1 24
Download 24 pages 47.47 Kb
Page 15
Image 15

COOL

The COOL jumper is used to determine the CFM during cooling operation. This jumper selection is activated for cooling when Y1 is energized.

The blower motor runs at 80 percent of the selected air flow for the first 7−1/2 minutes of each cooling demand. This feature allows for greater humidity removal and saves energy.

In the cooling mode, the blower control delays blower operation for 5 seconds after the compressor starts. The blower continues to operate for 90 seconds after the compressor is de−energized.

HEAT

The HEAT jumper is used to determine CFM during gas heat operation only. These jumper selections are activated only when W1 is energized.

In the heating mode, the blower control delays blower operation for 30 seconds after the flame is established. The

blower continues to operate for 90 seconds after the gas valve is de−energized.

CONTINUOUS FAN

When the thermostat is set for

and there is no demand for heating or cooling, the blower control will provide 50 percent of the COOL CFM selected.

NOTE − With the proper thermostat and subbase, continuous blower operation is possible by closing the R to G circuit. Cooling blower delay is also functional in this mode.

DEHUMIDIFICATION

The blower control includes an HUM terminal which provides for connection of a humidistat. The JV1 resistor on the blower control must be cut to activate the HUM terminal. The humidistat must be wired to open on humidity rise. When the dehumidification circuit is used, the variable speed motor will reduce the selected air flow rate by 25 percent when humidity levels are high. An LED (D1) lights when the blower is operating in the dehumidification mode.

Table 4

15GCSXAV−24, 15GCSXAV−30 Blower Performance

0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range

 

 

 

 

 

 

 

 

 

 

 

Jumper Speed Positions

 

 

 

 

 

 

 

 

 

 

 

ADJUST

 

 

Speed

 

 

 

 

 

 

 

T" Speed

 

 

 

 

 

FAN" Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

B

 

C

 

D

 

A

 

B

 

C

 

D

 

A

 

B

 

C

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

Jumper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

cfm

L/s

cfm L/s

 

cfm

L/s

cfm

L/s

cfm L/s

cfm L/s

cfm L/s

cfm L/s

cfm L/s

cfm L/s

 

cfm L/s

cfm L/s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

1150

545

920

435

 

690

325

1035 490

1265

595

1150

545

1035 490

920

435

575

 

270

460

215

 

345

165

520

245

NORM

1000

470

800

380

 

600

285

900

425

1100

520

1000 470

900

425

800

380

500

 

235

400

190

 

300

140

450

210

850

400

680

320

 

510

240

765

360

935

440

850

400

765

360

680

320

425

200

340 160

 

300

140

385

180

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 5

15GCSXAV−36 Blower Performance

0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range

 

 

 

 

 

 

 

 

 

 

Jumper Speed Positions

 

 

 

 

 

 

 

 

 

 

 

ADJUST

 

 

Speed

 

 

 

 

 

 

T" Speed

 

 

 

 

 

FAN" Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

B

 

C

 

D

 

A

 

B

 

C

 

D

 

A

 

B

 

C

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

Jumper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

cfm

L/s

cfm

L/s

cfm

L/s

cfm L/s

cfm L/s

cfm L/s

cfm L/s

cfm L/s

cfm L/s

cfm L/s

 

cfm L/s

cfm L/s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

1380

650

1150

545

920

435

1265 575

1555

735

1265 595

1150

545

1035 490

690

 

325

575

270

 

460

215

635

300

NORM

1200

565

1000 470

800

380

1100

520

1350

635

1100 520

1000 470

900

425

600

 

285

500

235

 

400

190

550

260

1020 480

850

400

680

320

935

440

1150 540

935

440

850

400

765

360

510

240

425 200

 

350

165

470

220

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 6

15GCSXAV−42, 15GCSX(A,B)V−48, 15GCSX(A,B)V−60, Blower Performance

0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range

 

 

 

 

 

 

 

 

 

Jumper Speed Positions

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed

 

 

 

 

 

 

T" Speed

 

 

 

 

FAN" Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Jumper

A

 

B

 

C

 

D

A

 

B

 

C

 

D

 

A

 

B

 

C

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

cfm

L/s

cfm L/s

 

cfm L/s

cfm L/s

cfm L/s

cfm L/s

 

cfm L/s

cfm L/s

cfm L/s

cfm L/s

 

cfm L/s

cfm L/s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

2070

975

1840 870

 

1610 760

1380 650

2015

950

1900 895

 

1555 735

1325 625

1035

490

920

435

 

805

380

690

325

NORM

1800

850

1600 755

 

1400 660

1200 565

1750

825

1650 780

 

1350 635

1150 545

900

425

800

380

 

700

330

600

285

1530

720

1360 640

 

1190

560

1020 480

1490

700

1405 660

 

1150

540

980

460

765

360

680

320

 

595

280

510

240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 