Lennox International Inc 51M32 Balance Point Setting, Service Indicator, Thermostat RESET

Models: 51M32

1 14
Download 14 pages 37.54 Kb
Page 11
Image 11
Balance Point

Display of Filter Reminder

ROOM 72

 

 

 

 

 

 

 

 

 

FILTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

 

 

 

AUTO

 

 

 

 

 

 

 

 

 

 

 

 

 

SYSTEM

 

 

HEAT

 

 

Figure 13

 

 

 

 

 

Balance Point

NOTE − The balance point is only available with the out- door sensor.

If the optional outdoor sensor (X2658) is connected to the thermostat, balance point adjustment is available. The bal- ance point feature allows the measured outdoor tempera- ture to govern operation of the heat pump and backup heat source.

Use the SETTINGS button to access the balance point set- ting. If the outdoor sensor is attached to the thermostat, press the SETTINGS button twice to access the Balance Point Settings screen (see figure 14).

Balance Point Setting

6P

SETPOINT 55

Figure 14

The balance point can be set at any temperature between 1°F and 55°F (−17°C to 13°C). A balance point setting of zero disables the balance point function (in this case, the thermostat behaves as if no outdoor sensor is attached). The default balance point setting is 55°F.

To adjust the balance point up or down, press the UP or

DOWN arrow keys to the right of the display screen. The balance point setting will increase by 1°F each time the UP key is pressed. The balance point setting will decrease by 1°F each time the DOWN key is pressed.

After the desired balance point is reached, the HOME screen will reappear after about eight seconds.

NOTE − The balance point feature allows the temperature to rise or fall 3°F above or below the setpoint. This prevents excessive cycling of the equipment when the outdoor tem- perature is near the balance point. For example, if the bal- ance point is 40°F and the actual outdoor temperature is 35°F, the outdoor temperature must rise to 43°F before equipment adjustment occurs. Conversely, if the balance point is 40°F and the actual outdoor temperature is 45°F, the outdoor temperature must drop to 37°F before equip- ment adjustment occurs.

Service Indicator

When abnormal equipment operation is detected, the SERVICE indicator will flash on the upper-right corner of the screen. This indicates that the equipment requires ser- vice from a qualified service technician. The SERVICE indi- cator is shown in figure 15.

Service Indicator Flashing

ROOM 73

SERVICE

 

FAN

 

AUTO

 

SYSTEM

 

HEAT

Figure 15

Thermostat RESET

Under some abnormal conditions, it may be desirable to re- set the thermostat to its default condition. The RESET but- ton can be used to return the unit to normal operation after an occurrence such as an electrical storm or power outage.

The RESET button is an unlabeled, recessed button lo- cated behind the door on the right−hand side of the thermo- stat, just below the SETTINGS button. The RESET button is visible in figure 3. Use a paper clip or small pencil to press the RESET button. After the RESET button is pressed, the thermostat settings will return to the defaults listed in the Default Settings section.

Page 5

Page 11
Image 11
Lennox International Inc 51M32 Balance Point Setting, Service Indicator, Thermostat RESET, Display of Filter Reminder