Default Thermostat Settings

Default Thermostat settings are in table 1.

Table 1

Default Thermostat Settings

Mode

Heat

 

 

Setpoint

70°F (or 21°C)

 

 

Fan

Auto

 

 

Filter Reminder

OFF (reminder setting = 0)

 

 

Equipment Protection

reset back to zero

Timers

 

 

 

Technical Specifications

Thermostat Type

Electronic nonprogrammable thermostat for 1H/1C, heat pump with electric or gas backup heat source, non−power robbing applications.

Power Supply Range

18VAC − 30VAC (24VAC nominal), 60Hz

Temperature Display

Display Scale: Fahrenheit or Celsius user selectable (via DIP switches)

Display range: 35°F (2°C) to 99°F (37°C)

Display resolution: 1°F (1°C)

Display Accuracy: +/−1°F

Temperature Measurement Range

Measurement Scale: Fahrenheit

Measurement Range: 35°F to 99°F

Measurement Resolution: 0.5°F

Measurement Accuracy: +/−1°F

Field Offset: via DIP switches to +/−3°F

Sampling Method: temperature measurements sampled every 15 seconds. Displayed temperature is the average of the last four measurements.

Temperature Setpoint Range

Setting range: 50°F (10°C) to 90°F (32°C)

Setting resolution: 1°F (1°C)

Fan Control

AUTO or ON modes.

Backup Heat Source Selection

Electric or gas furnace, selectable via DIP switch #5 (Aux or Dual, respectively). See also Thermostat Output section.

I/O Relays

All thermostat relays are latching type to minimize power consumption. See table 2.

 

Table 2

51M33 Terminal Designations

 

 

Connections

Description

 

 

O

Reversing valve, cool active

 

 

B

Reversing valve, heat active

 

 

R

24VAC

 

 

G

Fan control

 

 

Y1

First stage cooling/heating, compres-

 

sor generated

 

 

W1

Auxiliary heating, furnace generated

 

 

L

Service Indicator

 

 

C

24VAC common

 

 

E

Emergency heat

 

 

T

Outdoor temperature sensor

 

connection 1

 

 

T

Outdoor temperature sensor

 

connection 2

 

 

Equipment Protection Timers

Minimum Compressor OFF time: 5 minutes

Minimum Compressor ON time: 4 minutes

Minimum Furnace ON time: 3 minutes

Minimum backup furnace cycle time (elapsed time be- tween any furnace activation and the next furnace activa- tion): 6 minutes.

Minimum elapsed time between any compressor activation and the next compressor activation: 6 minutes.

NOTE − All protection timers (except the compressor OFF timer) can be over−ridden if a heating or cooling demand is initiated or terminated using the UP, DOWN, HEAT, or COOL buttons.

Equipment Protection Override

Both the minimum compressor OFF timer and the mini- mum equipment cycle timer can be over−ridden by press- ing and holding either the HEAT or COOL button down for 4 seconds.

Over−Temperature Protection

Thermal mechanical switch opens W1 at 93°F+/−6°F.

Filter Reminder

Settings of 0 (Off), 1, 3, 6 or 12 months are available. When programmed time has elapsed, a FILTER indicator is dis- played.

Balance Point

0°F (OFF) to 55°F, user selectable.

Page 6