Table 3

Thermostat Output States

Condition

W1

 

Y1

G

O

E

 

 

 

 

 

 

 

Electric Heat Backup − No Outdoor Sensor

 

 

 

 

 

 

 

 

 

 

 

small heat demand

 

 

X

X

 

 

 

 

 

 

 

 

 

large heat demand

X

 

X

X

 

 

 

 

 

 

 

 

 

emergency heat demand

 

 

 

X

 

X

 

 

 

 

 

 

 

cool demand

 

 

X

X

X

 

 

 

 

 

 

 

 

no demand

 

 

 

 

dc

 

 

 

 

 

 

 

Gas Heat Backup (Dual Fuel) − No Outdoor Sensor

 

 

 

 

 

 

 

 

 

 

small heat demand

 

 

X

X

 

 

 

 

 

 

 

 

 

large heat demand

X

 

 

 

 

 

 

 

 

 

 

 

 

emergency heat demand

 

 

 

 

 

X

 

 

 

 

 

 

 

cool demand

 

 

X

X

X

 

 

 

 

 

 

 

 

no demand

 

 

 

 

dc

 

 

 

 

 

 

 

 

Electric Heat Backup − Outdoor Sensor Attached

 

 

 

 

 

 

 

 

 

 

 

small heat demand (BBP)

 

 

X

X

 

 

 

 

 

 

 

 

 

large heat demand (BBP)

X

 

X

X

 

 

 

 

 

 

 

 

 

small heat demand (ABP)

 

 

X

X

 

 

 

 

 

 

 

 

 

large heat demand (ABP)

 

 

X

X

 

 

 

 

 

 

 

 

 

emergency heat demand

 

 

 

X

 

X

 

 

 

 

 

 

 

cool demand

 

 

X

X

X

 

 

 

 

 

 

 

 

no demand

 

 

 

 

dc

 

 

 

 

 

 

 

Gas Heat Backup (Dual Fuel) − Outdoor Sensor Attached

 

 

 

 

 

 

 

 

 

small heat demand (BBP)

X

 

 

 

 

 

 

 

 

 

 

 

 

large heat demand (BBP)

X

 

 

 

 

 

 

 

 

 

 

 

 

small heat demand (ABP)

 

 

X

X

 

 

 

 

 

 

 

 

 

large heat demand (ABP)

X

 

 

 

 

 

 

 

 

 

 

 

 

emergency heat demand

 

 

 

 

 

X

 

 

 

 

 

 

 

cool demand

 

 

X

X

X

 

 

 

 

 

 

 

 

no demand

 

 

 

 

dc

 

 

 

 

 

 

 

 

NOTE −

 

 

 

 

 

 

S X = output is activated with 24VAC

S dc: does not care (output can be in either state, i.e., either active or inactive)

S BBP: outdoor temperature is below balance point

S ABP: outdoor temperature is above balance point

S small heat demand: temperature is between (setpoint − 1.5°F) and (setpoint − 0.5°F), and 30-minute upstage timer has not expired (see Normal Heat Mode graph)

S large heat demand: temperature is below (setpoint − 1.5°F), or 30-minute upstage timer has expired (see Nor- mal Heat Mode graph)

S the state of the B terminal is opposite the state of the O terminal.

S data above are tabulated for AUTO fan setting. If fan setting is ON, the fan is activated in all cases.

Page 8