If the unit is installed in a residential garage, it must be located or protected to avoid physical damage by vehicles. The unit must be installed so that no electrical compo- nents are exposed to water.
I
[A CAUT,ON]
This unit must be installed level to allow for
proper drainage of the chassis base pan and
unit drain pan.
Installing With a Wall Sleeve
[ _, CAUTION l
The sleeve is not intended as the sole support for the unit. An additional support must be provided near the return opening on the unit for adequate support. The use of vibration isolation material between the unit and the
support is recommended.
Refer to the installation instructions packed with the wall sleeve and Figure 1 for guidance in assembly and mount- ing using a wall sleeve.
Make sure the gaskets attached to the sleeve are not damaged.
Seal the space between the wall sleeve
Assure that the unit is completely seated against the gaskets on the wall sleeve.
Installing Without a Wall Sleeve
Refer to the following directions and Figure I for guidance in installing the unit without a wall sleeve:
. Measure the size of the unit and provide an opening in an outside wall that will accept the unit. Local ordi- nances may require a steel lintel to support the wall above the opening. The opening must be square in all
4 corners.
,Position the unit so that the grilles on the outside face of the unit are flush or extend beyond the face of the exterior wall, but not recessed more than 2" from the face of the building. Provide a support under the unit, inside the building. Make sure that the inside
support does not block the return air. The unit should be installed level
. Seal the space between the unit and building opening using a
Condensate Drain
Install the plastic drain tube (furnished) over the 5/8" O.D. fitting welded to the center of the condensate pan. Con- nect the other end of the drain tube to trapped drain line (see Figure 2). The plastic drain connection to the chassis
base is provided so that it may be disconnected from the permanent drain tubing in the base of unit in the event it becomes necessary to remove the chassis assetnbly.
The drain line should pitch gradually downward at least 1" per 10 feet of horizontal run to the open drain.
Be certain that the plastic drain tubing has free drainage and is not crimped or flattened at any bend.
PWC Drain Installation
Drain Pan_
Figure 2
Limitations
The unit should be installed in accordance with all national and local safety codes.
Limitations of the unit and appropriate accessories must also be observed.
The unit must not be installed with any ductwork in the outdoor air stream. The outdoor fan is not designed to operate against any additional static pressure.
Minimum and maximum operation conditions must be observed to assure maximum system performance with minimum service required. Refer to Table 1 on page 4 for the application limitations of the unit.