The defrost controlwill initiate a defrosl cycle if the time period has elapsedand the defrost sensor detects a temperature below freezfng. At the slart of the defrost cycle, Ihe defrost ControlwUIenergize the reversing valve solenoid,shift(ng the reversing valve and
FIGURE3
OEFROST
TEST PINS
OEFROST
TIME JUMPER
T2 = 60 MINUTES
T1 = 30 MINUTES
T3 = 90 MINUTES
The defrost controlis alsoequippedwith a set of testpinsto aid in troubleshootingof thedefrost system.The follow- ing is a briefoutline of the testing of the defrost system.
The defrostsensorwilt be closedat 32 ° F or below. If temperaturesare such that the switch is not closed,jumper between the defrostsensorterminalson the defrostcontrol.
Start the systemin heating operation.
Jumper test pins. A 1/4" quick connectterminalcrimpedonto a solidwire or brazing rod workswell for testjumper. Closing test pins speed up time interval by a factor of 256.
DEFROSTCONTROLSETTINGDEFROSTTEST CYCLETIME
7 seconds | |
14 seconds | |
21 seconds |
After closingtest pinsand appropriatecycle timehas elapsed,the reversing valveshouldshift to defrostmodeand the outdoor fan should stop. Aftertwo secondsof defrostoperation, the reversing valve shouldshift back to heating operation and the outdoor fan shouldstart.
SYSTEM PERFORMANCE
For maximumperformanceof this heatpump system,the operatingtemperaturesand pressureshouldbe checked and superheat determined at Standard ARItest conditionsof 82°F outdoor - 80°F indoordry bulb/67°F wet burb. If the superheatmeasureddeviates from thevalues in the table below, the refrigerant charge shouldbe adjustedaccor- dingly for maximum performance.
PWC SUCTIONSUPERHEAT |
| |
Outdoor Unit Model | SuctionSuperheat@ A.R.I. Conditions | |
PWC182 |
| 18° . 20OF |
PWC242 |
| 17° - 19% |