The furnace must have a 115-v power supply properly connected
and grounded. Proper polarity must be maintained for correct
operation. Thermostat wire connections at R, W, C, and Y must be
made at the 24-v terminal block on the control board. The gas
service pressure must not exceed 0.5 psig (14-in. wc), but must be
no less than 0.16 psig (4.5-in. wc).
CAUTION: This furnace is equipped with a manual
reset limit switch or fuse link in the gas control area. The
switch or fuse link opens and shuts off power to the gas
valve if a flame rollout or overheating condition occurs in
the gas control area. DO NOT bypass the switch. Correct
inadequate combustion air supply problem and reset the
switch or replace the fuse link.
Before operating the furnace, check each manual reset switch for
continuity. If necessary, press the button to reset the switch.
The blower compartment door must be in place to complete the
115-v circuit to the furnace.
B. Sequence of Operation
CAUTION: Furnace control must be grounded for
proper operation, or control will lockout. Control is
grounded through green wire routed to gas valve and
burner bracket screw.
Using the schematic diagram shown in Fig. 11, follow the
sequence of operation through the different modes. Read and
follow the wiring diagram very carefully.
NOTE: If there is a power interruption and any thermostat call,
the control initiates a 90-sec blower only on period before starting
another cycle.
TABLE 5—ELECTRICAL DATA
UNIT SIZE VOLTS—
HERTZ—
PHASE
OPERATING
VOLTAGE RANGE MAXIMUM
UNIT AMPS MINIMUM
WIRE GAGE MAXIMUM
WIRE LENGTH (FT)‡
MAXIMUM
FUSE OR
HACR-TYPE CKT
BKR AMPS†
Maximum* Minimum*
024045 115—60—1 127 104 6.0 14 47 15
036045 115—60—1 127 104 8.3 14 34 15
024070 115—60—1 127 104 5.9 14 47 15
036070 115—60—1 127 104 8.7 14 32 15
042091 115—60—1 127 104 9.0 14 31 15
048091 115—60—1 127 104 10.4 14 27 15
036110 115—60—1 127 104 8.0 14 35 15
048111 115—60—1 127 104 10.1 14 28 15
060111 115—60—1 127 104 14.4 12 31 20
048135 115—60—1 127 104 10.1 14 28 15
060135 115—60—1 127 104 13.3 12 33 20
060155 115—60—1 127 104 14.0 12 31 20
* Permissible limits of the voltage range at which the unit operates satisfactorily.
† Time-delay fuse is recommended.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
Fig. 8—Heating and Cooling Application Wiring Diagram A95241
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
AUXILIARY
J-BOX
CONTROL
BOX
24-VOLT
TERMINAL
BLOCK
THREE-WIRE
HEATING-
ONLY
FIVE
WIRE
NOTE 1
NOTE 2
FIELD-SUPPLIED
FUSED DISCONNECT
CONDENSING
UNIT
TWO
WIRE
FURNACE
R
G
C
WCR GY
GND
GND
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
208/230- OR
460-VOLT
THREE
PHASE
208/230-
VOLT
SINGLE
PHASE
WHT
BLK
WHT
BLK
NOTES: Connect Y-terminal as shown for proper operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
W
Y
GND
THERMOSTAT
TERMINALS
1.
2.
3.
—8—