14. Installation

14.5Drain Pipe Work

Drain pipe gradient and support

1)- The drain pipe must be fitted at a gradient of at least 1/100.

- The drain pipe should be as short as possible and free from airlocks.

Indoor unit

Gradient of at least 1 / 100 (1cm/ 1m)

2)Suspension bolts should be used to support long stretches of drain pipe in order to ensure that a gradient of 1/100 is maintained.(PVC pipe should not be bent)

Spacing of supports for horizontal piping

Class

Nominal diameter

Spacing

 

 

 

Rigid PVC pipe

25~40mm

1.0m or less

 

 

 

3)The length of pipe laid horizontally should be kept a minimum.

Drain trap

Fit any indoor unit whose drain pipe connection is subjected to negative pressure, with a drain trap.

1) Rig the drain trap as shown in the drawing below

Indoor unit

H

H

H: 50mm or more

 

2)Provide one trap per unit. A single trap for converging units will prove ineffective.

3)Rig the trap to allow for future changing.

Plug

Indoor unit

Indoor unit

Plug