17
SPECIFICATIONS
Model Number PA350-120U PA500-120U
Model Rating VA / W 350/225 500 / 300
DIMENSIONS: in (mm)
Unit W x D x H 6.6 x 9.8 x 3.7
(168 x 250 x 95)
6.6 x 9.8 x 3.7
(168 x 250 x 95)
Shipping W x D x H 9.4 x 13.8 x 5.6
(238 x 350 x 142)
9.4 x 13.8 x 5.6
(238 x 350 x 142)
WEIGHT: lbs (kg)
Unit 11.7 (5.3) 13.5 (6.1)
Shipping 12.1 (5.5) 13.9 (6.3)
INPUT AC PARAMETERS
Surge Protection 603J
Voltage Range Without
Battery Operation 98VAC - 140 VAC ±3 VAC
Frequency 57 - 63 Hz (±0.4Hz)
Input Power Cord 6.5 ft.attached, w/ NEMA 5-15 P
OUTPUT AC PARAMETERS
Output Receptacles (3) NEMA 5-15R (orange) battery backup+surge protection
(2) NEMA 5-15R (black) surge protection
Voltage (Battery Mode) 120VAC ±8%
Output Current 2.9 A 4.2 A
Waveform (Battery Mode) Stepped Sinewave
Frequency (Battery Mode) 60Hz ±1Hz
Overload Warning >100%
Overload Shutdown >110%
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Rating 1 x 12V x 5 Ah 1 x 12V x 7 Ah
Transfer Time 4 – 6 ms typical
Back-up Time: At 77°F (25°C), resistive loading, w/ fully charged batteries:
Full load 5 minutes 3 minutes
Half load 16 minutes 15 minutes
Recharge Time 12 hours to 90% capacity, after full discharge into
resistive load
ENVIRONMENTAL
Operating Temperature +32°F to + 104°F (0°C to +40°C)
Storage Temperature +5°F to + 122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000 m) at 86°F (30°C) w/o derating
Audible Noise < 40 dBA, at 1 meter
AGENCY
Safety UL 1778, c-UL Listed
Surge ANSI C62.41, Category A, Level 3, (IEEE 587, Category A);
EN61000-4-5, Level 3, Criteria A
ESD EN61000-4-2, Level 3, Criteria A
Susceptibility EN61000-4-3, Level 2, Criteria A
Electrical Fast Transient/Burst EN61000-4-4, Level 3, Criteria A
Emissions FCC Part 15, Subpart B, Class B
Harmonics EN61000-3-2
Conducted Immunity EN61000-4-6
Flicker EN61000-3-3
Transportation ISTA Procedure 1A