SPECIFICATIONS

Model Number

PA350-120U

PA500-120U

Model Rating VA / W

350/225

500 / 300

DIMENSIONS: in (mm)

 

 

Unit W x D x H

6.6 x 9.8 x 3.7

6.6 x 9.8 x 3.7

(168 x 250 x 95)

(168 x 250 x 95)

 

Shipping W x D x H

9.4 x 13.8 x 5.6

9.4 x 13.8 x 5.6

(238 x 350 x 142)

(238 x 350 x 142)

 

WEIGHT: lbs (kg)

 

 

Unit

11.7 (5.3)

13.5 (6.1)

Shipping

12.1 (5.5)

13.9 (6.3)

INPUT AC PARAMETERS

 

 

 

Surge Protection

603J

 

Voltage Range Without

98VAC - 140VAC ±3VAC

Battery Operation

 

 

 

Frequency

57 - 63 Hz (±0.4Hz)

Input Power Cord

6.5 ft.attached, w/ NEMA 5-15 P

OUTPUT AC PARAMETERS

 

 

 

Output Receptacles

(3) NEMA 5-15R (orange) battery backup+surge protection

(2) NEMA 5-15R (black) surge protection

 

Voltage (Battery Mode)

120VAC ±8%

 

Output Current

2.9 A

 

4.2 A

Waveform (Battery Mode)

Stepped Sinewave

Frequency (Battery Mode)

60Hz ±1Hz

 

Overload Warning

>100%

 

Overload Shutdown

>110%

 

BATTERY PARAMETERS

 

 

 

Type

Valve-regulated, nonspillable, lead acid

Quantity x Voltage x Rating

1 x 12V x 5 Ah

 

1 x 12V x 7 Ah

Transfer Time

4 – 6 ms

typical

 

Back-up Time:

At 77°F (25°C), resistive loading, w/ fully charged batteries:

Full load

5 minutes

 

3 minutes

Half load

16 minutes

 

15 minutes

Recharge Time

12 hours to 90% capacity,

after full discharge into

resistive load

 

 

 

ENVIRONMENTAL

 

 

 

Operating Temperature

+32°F to + 104°F (0°C to +40°C)

Storage Temperature

+5°F to + 122°F (-15°C to +50°C)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000 m) at 86°F (30°C) w/o derating

Audible Noise

< 40 dBA, at 1 meter

AGENCY

 

 

 

Safety

UL 1778, c-UL Listed

Surge

ANSI C62.41, Category A, Level 3, (IEEE 587, Category A);

EN61000-4-5, Level 3, Criteria A

 

ESD

EN61000-4-2, Level 3, Criteria A

Susceptibility

EN61000-4-3, Level 2, Criteria A

Electrical Fast Transient/Burst

EN61000-4-4, Level 3, Criteria A

Emissions

FCC Part 15, Subpart B, Class B

Harmonics

EN61000-3-2

 

Conducted Immunity

EN61000-4-6

 

Flicker

EN61000-3-3

 

Transportation

ISTA Procedure 1A