DISCONTINUED

 

 

 

 

PRODUCT

 

 

 

 

 

PowerSure PSA

 

 

Quick-Start Guide for 350-1000VA; 120V

WHATS IN THE BOX

 

* Power ON/OFF/

*** USB port

Site Wiring Fault *

 

Indicator (Red)

Quick-Start guide

 

Alarm Silence

 

PowerSure PSA

* Utility Indicator

*** DB-9 port

DIP switches **

• PowerSure family user manual on CD (also at www.liebert.com)

 

(Green)

 

 

** Orange output recep-

Data Line ***

Warranty card

 

Battery Indicator *

 

tacles (battery backup

Protection

MultiLinksoftware CD

 

(Green/Amber)

and surge protection)

Connectors

• MultiLink serial cable (M3LS9P9S), 10 ft. (3m)

 

 

(4 receptacles on 350,

 

 

* Fault Indicator

500 and 650VA models)

 

RJ-11 cord, 7 ft. (2.1 m)

 

(Red/Green)

** Black output

 

• USB cable, 6 ft. (1.8m)

 

 

 

 

 

receptacles (surge

Battery cover plate

 

 

 

For details, see :

protection only)

For more details, refer to the PowerSure user manual on CD.

 

(on bottom for

 

* Controls and Indicators

 

650&1000VA models)

Para una información más detallada, consulte el manual del usuario

 

** Installation

6-ft. (1.8m)

(on rear of 350&500VA

de la familia PowerSure en el CD.

 

*** Communications

power cord

models)

 

 

INSTALLATION

Read all safety, installation and operating instructions in the PowerSure family user manual on the included CD or at www.liebert.com before operating the UPS. Adhere to all warnings on the unit and in the manual.

1.Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of 4 inches (100mm) on each side of the UPS. Maintain an ambi- ent temperature range of 32°F to 104°F (0°C to 40°C).

2.Plug the PSA’s power cord into an AC outlet. Check the Site Wiring Fault Indicator on the rear; if it is illuminated, refer to the Troubleshooting section.

3.Plug any computers and monitors into the orange receptacles for battery backup and surge protection; other office machines that do not exceed the capacity of the UPS may be plugged into either of the two (2) black receptacles, which provide surge protection only.

4.Connect Phone/Fax/DSL/Internet/Modem devices to data line connectors.

5.Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Utility Indi- cator will illuminate (green).

6.Turn on connected equipment.

Plug computers, monitors & network hubs into orange receptacles

Plug this type of equipment into black receptacles ONLY

Inkjet printers

Scanners

Fax machines

 

 

 

 

 

CONTROLS AND INDICATORS

COMMUNICATIONS

This button controls output power to the connected load and has three functions:

Turns the PowerSure PSA ON

Turns the PowerSure PSA OFF

Silences PowerSure PSA alarms

TURN THE UPS ON: Press and release the main ON/OFF button to start the UPS. An audible alarm will sound briefly.

TURN THE UPS OFF: When the PSA is ON, hold the main ON/OFF button down for more than 2 seconds to shut it down. An audible alarm will sound briefly.

SILENCE AN ALARM: When a UPS alarm is active, press and release the main ON/OFF button to silence the audible alarm (Exceptions: low battery, overload and overtemperature). DO NOT hold the button down for more than 2 seconds or the PSA will shut down.

The PowerSure PSA will communicate with your computer in either of two ways: over its DB-9 port through Lie- bert’s MultiLinksoftware or by USB through Microsoft® Windows® operating system features.

MultiLink supplies useful monitoring data, such as input voltage and battery level, and will perform an orderly shut- down of the computer system. Microsoft Windows XP and 2000 operating system utilities supply UPS status infor- mation and will perform an orderly computer shutdown. Check your computer’s OS features to determine whether it has power management capability.

For MultiLink Serial Communications

Connect the provided MultiLink serial cable to the DB-9 ports on the rear of the UPS and on the rear of your computer.

Install the MultiLink software—the software, installation instructions and the user manual are on the CD included in the PowerSure PSA package.

For USB Communications (with operating system power management)

Connect the USB cable provided with the UPS to the USB ports on the PSA and your computer. The PSA will work automatically with the built-in power management software on Windows XP and 2000 or later.

All USB models are compatible with Microsoft Windows 2000, Windows XP and Macintosh® OS 10.2 or later.

CHECK THE PSA’S CONDITION: Three status indicators on the front of the UPS illuminate to specify the status of the UPS (see Troubleshooting section for details).

Utility Indicator

Green: Normal operation

Amber: Buck/Boost

mode

Fault Indicator

 

Green:

Overload/

 

 

Overtemperature

Battery Indicator

Red:

UPS fault

Green: On battery

Amber: Battery warning

SITE WIRING FAULT INDICATOR (RED)

The Site Wiring Fault Indi-

Rear of UPS

cator on the rear panel, as

DIP Switches

shown, illuminates red

 

when the UPS detects a

 

line-neutral reversal or a

Site Wiring

poor neutral-ground. (See

Fault

Troubleshooting Chart if

Indicator

indicator is illuminated.)

(Red)

 

TRANSFER VOLTAGE SELECTORS (DIP SWITCHES)

The two-position DIP switch control on the rear panel, shown above, allows the operator to select the utility transfer voltage at which the UPS will switch to battery power. The factory default settings are 100VAC - 135VAC. DIP switch positions for each voltage setting are:

DIP switch settings

Left

Right

Nominal Utility

Setting

Up

Up

120VAC

85 - 145VAC (default)

Up

Down

110VAC

78 - 138VAC

Down

Up

127VAC

90 - 150VAC

Down

Down

120VAC

85 - 145VAC

CAUTION

! Never change the voltage settings while the UPS is ON and powering connected loads. Change DIP switches only when the UPS is OFF.

CAUTION

! To ensure protection of the connected equipment, the DIP switch settings should match the nominal utility input voltage. DIP switch settings not matching the nominal utility could potentially damage connected equipment.

SPECIFICATIONS

Model Number

PSA350MT-120

PSA500MT-120

PSA650MT-120

PSA1000MT-120

Power Rating VA/W

350VA/210W

 

500VA/300W

650VA/390W

1000VA/600W

DIMENSIONS: in. (mm)

 

 

 

 

 

Unit

4.6x7.7x8.7

 

4.6x7.7x8.7

4.6x14.1x8.7

4.6x14.1x8.7

WxDxH

(116x196x222)

 

(116x196x222)

(116x358x222)

(116x358x222)

Shipping

7.7x12.2x11.5

 

7.7x12.2x11.5

9.5x19.7x12.4

9.5x19.7x12.4

WxDxH

(196x310x293)

 

(196x310x293)

(242x500x316)

(242x500x316)

WEIGHT: lbs (kg)

 

 

 

 

 

Unit

16.8 (7.6)

 

17.2 (7.8)

20.7 (9.4)

29.7 (13.5)

Shipping

18.1 (8.2)

 

18.5 (8.4)

22.9 (10.4)

31.9 (14.5)

INPUT AC PARAMETERS

 

 

 

 

 

Surge Protection

 

 

570J

 

Voltage Range Without

78VAC - 150VAC, DIP switch selectable

Battery Operation

 

(see “DIP switch settings” on page 1)

Frequency Range

 

 

46.5 - 63.5 Hz (±0.1 Hz)

 

Input Power Cord

6 ft. (1.8m) attached, w/ NEMA 5-15 P

OUTPUT AC PARAMETERS

 

 

 

 

 

 

 

 

 

(6) NEMA 5-15R

 

(4) NEMA 5-15R (orange)

(orange) Battery

 

backup + surge

 

Battery backup + surge protection;

Output Receptacles

protection;

(2) NEMA 5-15R (black)

 

(2) NEMA 5-15R

 

 

 

Surge protection

 

 

 

 

 

(black) Surge

 

 

 

 

 

protection

Voltage (Normal mode)

 

 

Nominal (110, 120, 127VAC) ±10%

Voltage (Battery mode)

 

 

120VAC ±8%

 

Output Current

2.9 A

 

4.2 A

5.4 A

8.3 A

Waveform (Battery mode)

 

 

Stepped Sinewave

 

Frequency

 

 

50 Hz or 60 Hz; auto sensing

 

Overload Warning

 

>100%

 

(Normal & Battery modes)

 

 

 

 

 

 

 

Overload Shutdown

 

>110%

 

BATTERY PARAMETERS

 

 

 

 

 

Type

Valve-regulated, nonspillable, lead acid

QuantityxVoltagexRating

(1)x12Vx7Ah

 

(1)x12Vx9Ah

(1)x12Vx9Ah

(2)x12Vx7.5Ah

Transfer Time

 

 

4 - 6 ms typical

 

Backup Time:

At 77°F (25°C), resistive loading, with fully charged batteries:

Full Load

8 minutes

 

8 minutes

5 minutes

5 minutes

Half Load

26 minutes

 

24 minutes

16 minutes

18 minutes

Recharge Time

 

 

6 hours to 90% of rated capacity,

 

 

after full discharge into resistive load

 

 

ENVIRONMENTAL (ALL MODELS)

Operating

+32°F to +104°F

Temperature

(0°C to +40°C)

 

 

Storage

+5°F to +104°F

Temperature

(-15°C to +40°C)

Relative

0% to 95%, non-

Humidity

condensing

Operating

Up to 10,000 ft.

(3000m) at 86°F (30°C)

Elevation

without derating

 

Audible Noise

< 40 dBA, at 1 meter

 

 

AGENCY

 

 

 

Safety

UL 1778, c-UL Listed

 

 

 

ANSI C62.41, Category

Surge

A, Level 3

(IEEE 587, Category A);

 

EN61000-4-5, Level 3,

 

Criteria A

ESD

EN61000-4-2, Level 3,

Criteria A

 

Susceptibility

EN61000-4-3, Level 3,

Criteria A

 

Electrical Fast

EN61000-4-4, Level 4,

Transient/Burst

Criteria A

Emissions

FCC Part 15, Subpart B,

Class B

 

Conducted

EN61000-4-6, Level 3,

Immunity

Criteria A

Harmonics

EN61000-3-2

 

 

Flicker

EN61000-3-3

 

 

Transportation

ISTA Procedure 1A

 

 

Page 1
Image 1
Liebert PSA500MT-120 quick start WHAT’S in the BOX, Installation, Controls and Indicators Communications, Specifications

350, PSA650MT-120, PSA500MT-120, PSA1000MT-120 specifications

The Liebert PSA series includes a range of uninterruptible power supply (UPS) units designed to provide reliable power protection for critical electronics. The models PSA1000MT-120, PSA500MT-120, PSA650MT-120 are particularly noteworthy for their efficiency, advanced features, and user-friendly design, positioning them as ideal solutions for businesses needing uninterrupted power.

The Liebert PSA1000MT-120, rated at 1000 VA, is designed to support essential equipment during power disruptions. It features a compact design and is equipped with a pure sine wave output, ensuring compatibility with sensitive electronic devices. The UPS also includes an LCD display that provides real-time information on battery status, load levels, and operational metrics, allowing users to monitor power conditions easily. Its advanced battery management technology maximizes battery lifespan and provides notifications for battery replacement.

The PSA500MT-120 is a 500 VA model that serves as an entry-level solution for smaller devices and networks. It retains many of the same features as its higher-capacity counterparts, such as automatic voltage regulation (AVR), which corrects minor power fluctuations without relying on battery power. This feature not only conserves battery life but also ensures that connected equipment receives stable power. The compact form factor makes it easy to install in various environments, from small offices to retail locations.

The PSA650MT-120, with a capacity of 650 VA, strikes a balance between the two, making it a versatile choice for businesses with moderate power needs. Like the other models, it provides pure sine wave output and includes the AVR feature. Enhanced communication options, including USB and RS-232 ports, allow for seamless integration with monitoring and management software, facilitating proactive management of UPS status and performance.

All models in the PSA series are built with advanced technologies that guarantee reliability. Each unit comes with a built-in smart charger for rapid recharging and a compact footprint to save space in critical areas. Additionally, they feature multiple outlets to accommodate various devices, ensuring a wide range of applications, from networking and telecommunications to server rooms.

In summary, the Liebert PSA1000MT-120, PSA500MT-120, and PSA650MT-120 UPS models serve as essential components for ensuring power continuity in today’s technology-reliant environments. Their robust features, advanced technologies, and user-friendly designs make them ideal solutions for safeguarding critical electronic infrastructures against disruptive power events.