TROUBLESHOOTING
The information below indicates various symptoms a user may encounter in the event the PowerSure PSA experiences a problem.
Use this information to determine whether external factors caused the problem. See Troubleshooting Chart for suggested remedy.
Utility | 1. | The Fault indicator illuminates, indicating the UPS | |
Indicator |
| detected a problem. | |
Fault | Battery | 2. | An alarm sounds, alerting that the UPS requires |
Indicator | Indicator |
| attention. The alarm can be silenced except for low |
|
|
| battery, overload and overtemperature warning |
|
|
| conditions. |
|
| 3. | Utility and/or Battery indicators may be illuminated as |
|
|
| a diagnostic aid to the operator, as shown below: |
GUIDE TO STATUS INDICATORS
Fault | Utility | Battery |
| |
Indicator | Indicator | Indicator | Diagnosis/ | |
|
|
| Audible Alarm | |
|
|
|
| |
— | Green | — | Normal operation with utility power | |
ON | present; no beep. | |||
|
| |||
— | — | Green | UPS is operating on battery; beep | |
ON | every 10 seconds. | |||
|
| |||
— | — | Green | Battery test has been initiated; no | |
ON | beep. | |||
|
| |||
— | Green | Amber | Battery needs to be replaced; long | |
ON | Flashing | beep every minute. | ||
| ||||
— | — | Amber | Low battery warning; beep every | |
Flashing | ||||
|
| |||
Green | Green | — | Overload warning, load is >100%; | |
Flashing | ON | beep every | ||
| ||||
Green |
|
| Overload shutdown, load exceeds | |
— | — | UPS capacity (110%); continuous | ||
Flashing | ||||
|
| beep. | ||
|
|
| ||
|
|
|
| |
Green | Green |
| Overtemperature (overtemp) | |
— | warning; beep every 5 seconds | |||
ON | ON | |||
| (Normal mode). | |||
|
|
| ||
Green |
| Green | Overtemperature (overtemp) | |
— | warning; beep every 5 seconds | |||
ON | ON | |||
| (Battery mode). | |||
|
|
| ||
|
|
|
| |
Green |
|
| Overtemperature (overtemp) | |
— | — | shutdown; long beep every | ||
ON | ||||
|
| 5 seconds. | ||
|
|
| ||
|
|
|
| |
Red | Green | — | UPS is on, fault warning; | |
Flashing | ON | continuous beep. | ||
| ||||
Red | — | — | UPS has failed & shut down; | |
ON | continuous beep. | |||
|
|
TROUBLESHOOTING CHART
If the UPS fails to operate properly, turn off the unit and repeat the steps in the Installa- tion section of this manual. If the problem persists, refer to the chart below:
Problem | Cause | Solution | |
|
| Check the circuit protector on the rear of the | |
| Overload/Short | UPS. If it is tripped, reset it and restart the | |
UPS | UPS. | ||
Circuit | For further help, call your local dealer, | ||
will |
| Liebert representative or the Liebert | |
not |
| Worldwide Support Group. | |
start |
|
| |
Battery disconnected | Check for proper connection of battery or | ||
| |||
| or is completely | ||
| batteries. | ||
| discharged | ||
|
| ||
| UPS not plugged in | Plug in the power cord securely. | |
|
|
| |
| Circuit protector | Reset the circuit protector and restart the | |
| tripped | UPS. | |
UPS starts | Power not available | Have the utility checked by a qualified | |
on battery, | at utility receptacle | electrician. | |
but will |
|
| |
| Wait until the voltage rises to an appropriate | ||
not switch | Input voltage | ||
to AC | below threshold | level or have the utility checked by a | |
|
| qualified electrician. | |
| AC overvoltage | Wait until voltage lowers to an appropriate | |
| level or have the utility checked by a | ||
|
| qualified electrician. | |
| Overload/Short | Check the circuit protector on the rear of the | |
| Circuit | UPS. If it is tripped, reset it and restart the | |
|
| UPS. | |
|
| ||
|
| If the problem persists, disconnect some of | |
UPS |
| the equipment from your | |
Internal UPS fault | wattage of your equipment must not exceed | ||
shuts | the capacity of the UPS. | ||
down, |
| For further help, call your local dealer, | |
Fault |
| Liebert representative or the Liebert | |
Indicator |
| Worldwide Support Group. | |
lit | High temp shutdown | Make sure that the UPS is operating in 32°F | |
| to 104°F (0°C to 40°C) and that it has | ||
|
| adequate ventilation. | |
| MultiLink shutdown | Consult the MultiLink user manual or contact | |
| your LAN administrator. | ||
|
| ||
Site Wiring | Have the utility checked by a qualified | ||
Fault | reversal, | ||
Indicator | Poor ground | electrician. | |
illuminated | connection |
| |
UPS not | Overload | Reduce load. | |
|
| ||
Battery not charged |
| ||
providing |
| ||
due to a recent | Recharge battery. | ||
expected | |||
outage |
| ||
| |||
|
| ||
time | Battery needs to be | Replace battery. | |
| replaced | ||
|
|
MAINTENANCE
The PowerSure PSA UPS requires very little maintenance. Follow these practices to prevent problems.
CLEANING THE UPS
The following will help ensure
•Vacuum dust from the ventilation intake occasionally.
•Wipe the cover periodically with a dry cloth.
MAINTAINING BATTERIES
The batteries are
When storing the UPS, it is recommended to plug in the UPS for at least 24 hours every four to six months to ensure full recharge of the batteries.
BATTERY REPLACEMENT
CAUTION
! A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the batteries:
• Remove rings, watches, and other metal objects.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact your local dealer or Liebert representative imme-
diately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Dispose of old batteries according to local codes.
This UPS is equipped with internal “hot swappable” batteries that the user can replace without shutting down the UPS or connected loads.
NOTE
Caution should be exercised when replacing the batteries because the load is unprotected from disturbances and power outages during this procedure.
PRODUCT WARRANTY REGISTRATION
To register for warranty protection: | If you have any questions, please | |
• Visit the Quick Links section of our | contact us at: | |
Web site at: | US: | |
http://www.liebert.com | ||
Outside the US: | ||
• Click on Product Warranty | ||
upstech@liebert.com | ||
Registration and fill in the form. | ||
|
BATTERY REPLACEMENT
Replacement requires removing the battery cover plate on the bottom of the UPS. No tools are needed.
To replace the batteries:
1. | Remove the battery | Figure 1 | Figure 2 |
| cover plate on the |
|
|
| back/bottom of the |
|
|
| UPS (Figure 1). |
|
|
2. | Pull the white tabs |
|
|
| towards you to |
|
|
| remove the battery |
|
|
| from the UPS |
|
|
| (Figure 2). |
|
|
3. | Disconnect the insu- | Figure 3 | Figure 4 |
| lated connectors |
|
|
from the battery ter- minals (Figure 3).
4. Insert a new battery pack, and push the connectors onto the battery terminals (black to black & red to red) (Figure 4).
NOTE: There may be a small spark at the battery terminals when reconnecting the connectors. This is normal and will not harm you or the UPS.
5. Push the battery | Figure 5 | Figure 6 |
pack into the UPS |
|
|
(Figure 5). |
|
|
6. Reattach the battery cover plate (Figure 6).