TROUBLESHOOTING

TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the PowerSure PSA experiences a problem.

Use this information to determine whether external factors caused the problem. See Troubleshooting Chart for suggested remedy.

Utility

1.

The Fault indicator illuminates, indicating the UPS

Indicator

 

detected a problem.

Fault

Battery

2.

An alarm sounds, alerting that the UPS requires

Indicator

Indicator

 

attention. The alarm can be silenced except for low

 

 

 

battery, overload and overtemperature warning

 

 

 

conditions.

 

 

3.

Utility and/or Battery indicators may be illuminated as

 

 

 

a diagnostic aid to the operator, as shown below:

GUIDE TO STATUS INDICATORS

Fault

Utility

Battery

 

Indicator

Indicator

Indicator

Diagnosis/

 

 

 

Audible Alarm

 

 

 

 

Green

Normal operation with utility power

ON

present; no beep.

 

 

Green

UPS is operating on battery; beep

ON

every 10 seconds.

 

 

Green

Battery test has been initiated; no

ON

beep.

 

 

Green

Amber

Battery needs to be replaced; long

ON

Flashing

beep every minute.

 

Amber

Low battery warning; beep every

Flashing

half-second.

 

 

Green

Green

Overload warning, load is >100%;

Flashing

ON

beep every half-second.

 

Green

 

 

Overload shutdown, load exceeds

UPS capacity (110%); continuous

Flashing

 

 

beep.

 

 

 

 

 

 

 

Green

Green

 

Overtemperature (overtemp)

warning; beep every 5 seconds

ON

ON

 

(Normal mode).

 

 

 

Green

 

Green

Overtemperature (overtemp)

warning; beep every 5 seconds

ON

ON

 

(Battery mode).

 

 

 

 

 

 

 

Green

 

 

Overtemperature (overtemp)

shutdown; long beep every

ON

 

 

5 seconds.

 

 

 

 

 

 

 

Red

Green

UPS is on, fault warning;

Flashing

ON

continuous beep.

 

Red

UPS has failed & shut down;

ON

continuous beep.

 

 

TROUBLESHOOTING CHART

If the UPS fails to operate properly, turn off the unit and repeat the steps in the Installa- tion section of this manual. If the problem persists, refer to the chart below:

Problem

Cause

Solution

 

 

Check the circuit protector on the rear of the

 

Overload/Short

UPS. If it is tripped, reset it and restart the

UPS

UPS.

Circuit

For further help, call your local dealer,

will

 

Liebert representative or the Liebert

not

 

Worldwide Support Group.

start

 

 

Battery disconnected

Check for proper connection of battery or

 

 

or is completely

 

batteries.

 

discharged

 

 

 

UPS not plugged in

Plug in the power cord securely.

 

 

 

 

Circuit protector

Reset the circuit protector and restart the

 

tripped

UPS.

UPS starts

Power not available

Have the utility checked by a qualified

on battery,

at utility receptacle

electrician.

but will

 

 

 

Wait until the voltage rises to an appropriate

not switch

Input voltage

to AC

below threshold

level or have the utility checked by a

 

 

qualified electrician.

 

AC overvoltage

Wait until voltage lowers to an appropriate

 

level or have the utility checked by a

 

 

qualified electrician.

 

Overload/Short

Check the circuit protector on the rear of the

 

Circuit

UPS. If it is tripped, reset it and restart the

 

 

UPS.

 

 

 

 

If the problem persists, disconnect some of

UPS

 

the equipment from your UPS—the total

Internal UPS fault

wattage of your equipment must not exceed

shuts

the capacity of the UPS.

down,

 

For further help, call your local dealer,

Fault

 

Liebert representative or the Liebert

Indicator

 

Worldwide Support Group.

lit

High temp shutdown

Make sure that the UPS is operating in 32°F

 

to 104°F (0°C to 40°C) and that it has

 

 

adequate ventilation.

 

MultiLink shutdown

Consult the MultiLink user manual or contact

 

your LAN administrator.

 

 

Site Wiring

Line-neutral

Have the utility checked by a qualified

Fault

reversal,

Indicator

Poor ground

electrician.

illuminated

connection

 

UPS not

Overload

Reduce load.

 

 

Battery not charged

 

providing

 

due to a recent

Recharge battery.

expected

outage

 

back-up

 

 

 

time

Battery needs to be

Replace battery.

 

replaced

 

 

MAINTENANCE

The PowerSure PSA UPS requires very little maintenance. Follow these practices to prevent problems.

CLEANING THE UPS

The following will help ensure trouble-free operation for years:

Vacuum dust from the ventilation intake occasionally.

Wipe the cover periodically with a dry cloth.

MAINTAINING BATTERIES

The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their design life. The UPS continuously charges the batteries when connected to the utility supply, even while the UPS is switched off.

When storing the UPS, it is recommended to plug in the UPS for at least 24 hours every four to six months to ensure full recharge of the batteries.

BATTERY REPLACEMENT

CAUTION

! A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the batteries:

• Remove rings, watches, and other metal objects.

• Do not lay tools or other metal objects on top of the batteries.

• If the battery replacement kit is damaged in any way or shows signs of leakage, contact your local dealer or Liebert representative imme-

diately.

• Do not dispose of batteries in a fire. The batteries may explode.

• Dispose of old batteries according to local codes.

This UPS is equipped with internal “hot swappable” batteries that the user can replace without shutting down the UPS or connected loads.

NOTE

Caution should be exercised when replacing the batteries because the load is unprotected from disturbances and power outages during this procedure.

PRODUCT WARRANTY REGISTRATION

To register for warranty protection:

If you have any questions, please

• Visit the Quick Links section of our

contact us at:

Web site at:

US: 800-222-5877

http://www.liebert.com

Outside the US: 614-841-6755

• Click on Product Warranty

upstech@liebert.com

Registration and fill in the form.

 

BATTERY REPLACEMENT

Replacement requires removing the battery cover plate on the bottom of the UPS. No tools are needed.

To replace the batteries:

1.

Remove the battery

Figure 1

Figure 2

 

cover plate on the

 

 

 

back/bottom of the

 

 

 

UPS (Figure 1).

 

 

2.

Pull the white tabs

 

 

 

towards you to

 

 

 

remove the battery

 

 

 

from the UPS

 

 

 

(Figure 2).

 

 

3.

Disconnect the insu-

Figure 3

Figure 4

 

lated connectors

 

 

from the battery ter- minals (Figure 3).

4. Insert a new battery pack, and push the connectors onto the battery terminals (black to black & red to red) (Figure 4).

NOTE: There may be a small spark at the battery terminals when reconnecting the connectors. This is normal and will not harm you or the UPS.

5. Push the battery

Figure 5

Figure 6

pack into the UPS

 

 

(Figure 5).

 

 

6. Reattach the battery cover plate (Figure 6).