FS-8704-02_BacnetEthernet.doc Driver Manual

Page 8 of 20

4.4.Client Side Map Descriptors

4.4.1.FieldServer Related Map Descriptor Parameters

 

 

Column Title

 

Function

 

 

Legal Values

 

 

Map_Descriptor_Name

 

Name of this Map

 

 

Up to 32 alphanumeric

 

 

 

 

 

Descriptor

 

 

characters

 

 

 

 

 

Name of Data Array where

 

One of the Data Array names

 

 

Data_Array_Name

 

data is to be stored in the

 

from “Data Array” section

 

 

 

 

 

FieldServer

 

 

above

 

 

Data_Array_Offset

 

Starting location in Data

 

 

0 to maximum specified in

 

 

 

Array

 

 

“Data Array” section above

 

 

 

 

 

 

 

 

 

Function

 

 

Function of Client Map

 

 

RDBC

 

 

 

 

Descriptor

 

 

 

 

 

 

 

 

 

 

4.4.2.

Driver Related Map Descriptor Parameters

 

 

 

 

 

 

 

 

 

 

Column Title

Function

 

 

 

Legal Values

 

 

Node_Name

 

 

Name of Node to

 

One of the node names specified in

 

 

 

 

fetch data from

 

“Client Node Descriptor” above

 

 

 

 

 

 

 

 

Data_Type

 

 

Data type

 

Note 2

 

 

Property

 

 

The BACnet

 

Present_Value

 

 

 

 

property to be read

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data_Array_Low_Scale*

Scaling zero in

 

-32767 to 32767, 0

 

 

Data Array

 

 

 

 

 

 

 

 

 

 

 

 

Data_Array_High_Scale*

Scaling max in Data

 

-32767 to 32767, 10000

 

 

Array

 

 

 

Node_Low_Scale*

Scaling zero in

 

-32767 to 32767, 0

 

 

Connected Node

 

 

 

 

 

 

 

 

 

 

 

 

Node_High_Scale*

Scaling max in

 

-32767 to 32767, 100

 

 

Connected Node

 

 

 

 

 

 

 

 

 

 

4.4.3.Timing Parameters

Column Title

Function

Legal Values

Scan_Interval

Rate at which data is polled

0-32000s, 20s

Note 2

AI

- ANALOG INPUT

BV

- BINARY_VALUE

AO

- ANALOG_OUTPUT

MI

- MULTI_STATE_INPUT

AV

- ANALOG_VALUE

MO

- MULTI_STATE_OUTPUT

BI

- BINARY_INPUT

MV

- MULTI_STATE_VALUE

BO

- BINARY_OUTPUT

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com