Chapter 4 Tabs 7
GXT3 Configuration Program User Manual
Figure 4-3 Options Tab
Note
In the Options Tab, the UPS must be in Standby mode for the setting to take effect.
Disable output - manual restart only
For particular industrial applications and special computer applications, the UPS may be monitored and controlled
using external voltages and relay contact signals.
An Any Mode Shutdown command can be activated on the terminal block of the UPS by operating Pin1 & Pin2.
If selected, the Disable Output Manual Restart Only setting will require the UPS to be manually restarted by
pressing the Start button on the front panel of the UPS after the Any Mode Shutdown signal on the terminal block has
been removed.
Note
If the UPS is in a remote location with limited access then the setting should not be used.
Auto-enable output automatically
For particular industrial applications and special computer applications, the UPS may be monitored and controlled
using external voltages and relay contact signals.
An Any Mode Shutdown command can be activated on the terminal block of the UPS by operating Pin1 & Pin2.
If selected, the Auto-Enable Output Automatically setting will automatically restore the UPS output after Any Mode
Shutdown signal on the terminal block has been removed.
Default operation - normally open
The shutdown logic can be configured for normally open or normally closed. This setting defines the configuration of
the Any Mode Shutdown.
If selected, the Any Mode Shutdown will operate when Pin1 & Pin2 of the terminal block are connected
Inverted operation - normally closed
The shutdown logic can be configured for normally open or normally closed. This setting defines the configuration of
the Any Mode Shutdown.
If selected, the Any Mode Shutdown will operate when Pin1 & Pin2 of the terminal block are disconnected.
4.3 Battery Tab
Select the Battery Tab, as shown in Figure 4-4.