Communications

7.0COMMUNICATIONS

7.1COMMUNICATIONS INTERFACE PORT

The UPStation GXT 2U UPS has a standard DB-9 serial port female connector located on the rear of the UPS unit. Several signals are pro- vided on this port and are assigned as follows:

Pin

 

 

 

 

Assignment Description

 

 

 

 

 

 

 

 

 

 

 

1

 

Low Battery (open collector)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

UPS TxD (typical RS-232 levels)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

UPS RxD (typical RS-232 levels)

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

Remote Shutdown (5-12VDC, 10-24 mA max); battery operation

 

 

 

 

 

 

 

 

 

 

 

 

5

 

Common

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

Remote Shutdown (short to pin 5); all modes of operation

 

 

 

 

 

 

 

 

 

 

 

7

 

Low Battery (open emitter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

Utility Fail (open emitter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

Utility Fail (open collector)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pin Assignment

 

 

 

Collector to Emitter*

 

 

 

 

 

 

 

 

 

 

 

 

 

6

7

8

9

 

 

 

 

 

 

(+)

Open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Collector

 

 

 

 

 

 

 

 

330 Ohms

 

 

 

 

 

 

 

 

 

 

1

 

2

3

4

5

 

 

 

(-)

Open

 

 

 

 

 

 

 

Emitter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Maximum voltage and current on pins 1, 7, 8, and 9 is 60VDC; 10.0 mA.

19

Page 23
Image 23
Liebert GXT 2U user manual Communications Interface Port