Configuration Program
8.0CONFIGURATION PROGRAM
The configuration program included with the UPStation GXT 2U line allows modification of several UPS settings that were previously unavailable or required custom manufacturing. The user manual on the configuration program disk describes the features available for modification, as well as default settings.
NOTE
The UPS must be turned
While the UPS is in Normal Mode operation, press the OFF button once to put the UPS into Bypass Mode.
Once the UPS is in Bypass Mode operation, press and release the OFF button two distinct times (for about a second each time) to turn off the UPS.
8.1GXT 2U CONFIGURATION PROGRAM ABILITIES
•Select one of five output voltages to match voltages found around the world.
•Enable/Disable
•Select frequency converter operation with a fixed output frequency of 50 or 60 Hz.
•Set the Low Battery Warning alarm time from 2 to 30 minutes.
•Enable/Disable the
•Set the
•Select the number of external battery cabinets connected to the UPS to adjust the remaining run time calculations reported by Liebert software products.
•Modify the shutdown setting of
NOTE
This program is compatible with UPS models beginning with
8.1.1What You Will Need
Using this program requires a computer running Windows
(95 through Server 2003), as well as the configuration program disk and serial cable included in the UPS accessory box. Use the serial cable (beige or tan,
Note: The black ML9P9S contact closure communication cable is NOT compatible with the configuration program.
23