Specifications
21
8.0 SPECIFICATIONS

Table 6 Liebert PSI XR specifications

Model Number PS1000RT3-120XR
PS1000RT3120XRW
PS1500RT3-120XR
PS1500RT3120XRW
PS2200RT3-120XR
PS2200RT3120XRW
PS3000RT3-120XR
PS3000RT3120XRW
Power Rating, VA/W 1000VA/900W 1500VA/1350W 1920VA/1920W*3000VA/2700W
Dimensions, W x D x H, in (mm)
Unit 17.3 x 19.3 x 3.5
(440 x 490.5 x 88)
17.3 x 19.3 x 3.5
(440 x 490.5 x 88)
17.3 x 27.6 x 3.5
(440 x 700.5 x 88)
17.3 x 27.6 x 3.5
(440 x 700.5 x 88)
Shipping 22 x 24.1 x 9
(560 x 612 x 228)
22 x 24.1 x 9
(560 x 612 x 228)
22 x 34.8 x 9.0
(560 x 884 x 228)
22.0 x 34.8 x 9
(560 x 884 x 228)
Weight, lb (kg)
Unit 56 (25) 62 (28) 92 (42) 105 (48)
Shipping 64 (29) 70 (32) 101 (46) 115 (52)
Input AC Parameters
Surge Protection 570J
Voltage Range
Without Battery Operation 83 to 159 VAC (configurable)
Frequency Range 45~65Hz, (±0.5Hz)
Input Power Cord,
10ft (3m) attached NEMA 5-15P plug NEMA 5-15P plug NEMA 5-20P plug NEMA L5-30P plug
Output Receptacles (6) NEMA 5-15R (6) NEMA 5-15R
(4) NEMA 5-15R
(2) NEMA 5-20R T-Slot,
accepts15A Plug
(4) NEMA 5-15R
(2) NEMA 5-20R T-Slot,
accepts15A Plug
(1) NEMA L5-30R
Voltage (Normal Mode) 110/120/127 VAC (configurable)
Voltage (Battery Mode) 110/120/127 VAC; ±5% before low-battery warning
Transfer Time 4-6 ms typical
Battery Waveform Sinewave
Battery Parameters
Type Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Ah 4 x 12 x 7.2 4 x 12 x 9 8 x 12 x 7.2 8 x 12 x 9
Recharge Time 5 hours to 90% of rated capacity, after full discharge into resistive load
Battery Backup Time
Full Load 5 minutes
Half Load 10 minutes
Environmental
Operating Temperature, °F (°C) 32 to 104 (0 to 40)
Storage Temperature, °F (°C) 5 to 104 (-15 to 40)
Relative Humidity 0% to 90%, non-condensing
Operating Altitude Up to 3000m (10,000 ft)
Audible Noise <40 dBA, internal fan(s) Off; <45 dBA, internal fan(s) On
Agency
Safety UL 1778, c-UL Listed
Emissions FCC Part 15, Class A
Network Surge UL 497 B
Transportation ISTA Procedure 1A Certification
* NEC limits the input current rating of the PS2200RT3-120XR and PS2200RT3120XRW models to 80% of the input plug's rating. Up to
2200VA/1980W is available by contacting a certified electrician to change the input plug to 30A plug. Emerson Network Power assumes no
liability for damage caused by miswiring or misapplication of the input plug.