Installation
3.0 INSTALLATION
3.1 Preparation
! CAUTION
The UPS and battery cabinets are heavy (see Table 6 and Table 7). Take proper precautions when lifting or moving either the UPS or battery cabinets.
The Liebert PSI XR may be installed in either a tower or rack configuration. Determine the method that suits the application and proceed.
Decide where to install the Liebert PSI XR. The UPS must be installed indoors in a controlled envi- ronment. Place it in an area with unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives and conductive contaminants (see Figure 6).
Maintain a minimum clearance of 12 inches (305mm) in the front and rear of the UPS. Maintain an ambient temperature range of 32°F to 104°F (0°C to 40°C).
Figure 6 Placing the Liebert PSI XR
AI | R |
R | I |
| A |
|
|
|
|
| A | |
|
|
|
|
| I | |
|
|
|
|
| R | |
|
|
|
|
|
| m |
|
|
|
|
| m | |
|
|
|
| 5 |
| |
|
|
| 0 |
|
| |
|
| 3 |
|
|
| |
| ./ |
|
|
|
| |
2 in |
|
|
|
|
| |
1 |
|
|
|
|
|
|
32 F (0 C) | 104 F (40 C) |
Relative humidity | 0% ~ 90% |
|
7