Table 5

Connection Type / Wire Size Range

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection Type

 

 

UPS Module

 

 

 

 

 

 

Rating

 

AC Input

Battery

 

Bypass Input

Neutral

Ground

kVA

 

 

& AC Output

10 - 30

 

Compression

Compression

 

Compression

Compression

Ground studs

 

 

lug

lug

 

lug

lug

3/8" - 16 x 1.00"

 

 

#14 to #1/0

#14 to #1/0

 

#14 to #1/0

#14 to #1/0

Lug required

 

 

 

 

 

 

 

 

40 - 50

 

Compression

Compression

 

Compression

Natural studs

Ground studs

 

 

lug

lug

 

lug

3/8" - 16 x 1.00"

3/8" - 16 x 1.00"

 

 

#6 to 250 kcmil

#6 to 250 kcmil

 

#6 to 250 kcmil

Lug required

Lug required

 

 

 

 

 

 

 

65 - 125

 

Bus bars (2” x 3-1/4”) with connecting hardware (3/8”) are provided for all power wiring

 

 

 

terminations. A field-supplied lug is required.

 

 

 

 

 

 

 

 

 

Use factory supplied connections for terminations where they are provided. Refer to Figure 16 for field- supplied wiring termination details. Use commercially available UL listed solderless lugs for the wire size required for your application. Connect wire to the lug using tool and procedure specified by the lug manufacturer.

Table 6

Torque Specifications (Unless Otherwise Labeled)

 

 

 

 

 

 

 

 

 

Nut and Bolt Combinations

 

 

 

 

 

 

 

 

 

Grade 2

Electrical Connections

 

 

 

 

Standard

with Belleville Washers

 

 

 

 

 

 

 

 

 

Bolt Shaft Size

 

Lb-in

 

N-m

Lb-in

N-m

 

1/4

 

53

 

6.0

46

5.2

 

 

 

 

 

 

 

 

 

5/16

 

107

 

12.1

60

6.8

 

 

 

 

 

 

 

 

 

3/8

 

192

 

21.7

95

10.7

 

 

 

 

 

 

 

 

 

1/2

 

428

 

48.4

256

28.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Block Compression Lugs

 

 

 

 

 

 

UPS Module

 

 

 

Wire Size or

 

 

 

Rating

 

Wiring

 

Lb-in

N-m

 

kVA

 

 

Range

 

10 - 125

 

Control

 

#22 - #14

3.5 to 5.3

0.4 to 0.6

 

 

 

 

 

 

 

 

 

10 - 30

 

Power

 

#6 - #1/0

50

5.6

 

 

 

 

 

 

 

 

 

40 - 50

 

Power

 

#6

250

28.2

 

 

 

 

 

 

 

 

 

 

 

 

 

250 kcmil

275

31.1

 

 

 

 

 

 

 

 

Installation 17

Page 25
Image 25
Liebert Series 300 manual Connection Type / Wire Size Range