Table 8

Alarm Messages (continued)

 

 

Alarm

Meaning and

Message

Corrective Action in Brackets [ ]

UPS SYSTEM (continued)

 

 

 

 

External shutdown

 

The UPS has been shut down from an external contact.

 

 

[Perform a UPS start-up procedure when the conditions causing the external

 

 

shutdown have been corrected.]

 

 

 

COOLING

 

 

 

 

 

Fan failure

 

A failure has been detected in at least one of the internal cooling fans.

 

 

[Contact Liebert Customer Service and Support.]

 

 

System shutdown impending due to

An overtemperature condition is present in the UPS cabinet. The UPS will

overtemperature

 

automatically shutdown if the overtemperature continues.

 

 

[Determine the cause of the condition and correct it if possible. Check for

 

 

clogged air filter, restricted air flow, or fan failure.]

 

 

System shutdown in 5 minutes due to

Overtemperature condition has persisted. Note the time stamp on the alarm

overtemp

 

message.

 

 

[Perform an orderly shutdown of the critical load. Perform a UPS shutdown

 

 

procedure or allow the UPS to perform an automatic shutdown. Contact Liebert

 

 

Customer Service and Support.]

 

 

 

Operation 65

Page 73
Image 73