Liebert Series 300 manual UPS System

Models: Series 300

1 125
Download 125 pages 60.86 Kb
Page 72
Image 72

Table 8

Alarm Messages (continued)

 

 

Alarm

Meaning and

Message

Corrective Action in Brackets [ ]

UPS SYSTEM

 

 

 

 

UPS output not synchronized to input

UPS inverter output is not synchronized with the input power. Automatic

power

 

transfers to the Static Bypass Line are prohibited. This is usually a temporary

 

 

condition that is corrected automatically by the UPS internal control system.

 

 

Input power single phased

This message indicates an input power problem.

 

 

[Check all input power phases.]

 

 

Input voltage sensor failed

Each input voltage phase has two sensors. One of these sensors has failed.

 

 

[Contact Liebert Customer Service and Support.]

 

 

Inverter leg over current in X-phase

A fault has been detected in the inverter, caused by a UPS failure. The load

 

 

has been automatically transferred to the Static Bypass Line. Power to the load

 

 

is not being conditioned by the UPS.

 

 

[Contact Liebert Customer Service and Support.]

 

 

 

Output undervoltage

 

UPS output voltage is below a specified minimum. The load has been

 

 

automatically transferred to the Static Bypass Line. Power to the load is not

 

 

being conditioned by the UPS. An automatic retransfer will be attempted when

 

 

the output voltage is within tolerance.

 

 

[Contact Liebert Customer Service and Support if this condition persists.]

 

 

 

Output overvoltage

 

UPS output voltage is above a specified maximum. The load has been

 

 

automatically transferred to the Static Bypass Line. Power to the load is not

 

 

being conditioned by the UPS. An automatic retransfer will be attempted when

 

 

the output voltage is within tolerance.

 

 

[Contact Liebert Customer Service and Support if this condition persists.]

 

 

 

Output overcurrent

 

An output overcurrent surge has been detected. The load has been

 

 

automatically transferred to the Static Bypass Line. An automatic retransfer will

 

 

be attempted when the output current returns to nominal.

 

 

[Contact Liebert Customer Service and Support if this condition persists.]

 

 

System output overloaded

An overload condition is present. If the load is on the UPS inverter, the load will

 

 

be automatically transferred to the Static Bypass Line if the overload exceeds

 

 

the UPS Module capacity.

 

 

[Determine cause of the overload and reduce the load.]

 

 

Load transferred to bypass due to

The load has been automatically transferred to the Static Bypass Line because

overload

 

of an overload condition.

 

 

[Determine cause of the overload and reduce the load.]

 

 

System output overloaded

The overload condition is still present and must be reduced or it will soon

 

 

exceed the capacity of the Static Bypass Line, resulting in loss of all power to

 

 

the critical load. Power to the load is not being conditioned by the UPS.

 

 

[Determine cause of the overload and reduce the load.]

 

 

System shutdown due to overload

An overload condition has exceeded the capacity of the Static Bypass Line.

 

 

The UPS has been shut down, resulting in loss of power to the critical load.

 

 

[Perform a UPS shutdown procedure. Correct the overload condition and

 

 

perform a UPS start-up procedure.]

 

 

 

Control error

 

Automatic diagnostic testing has detected a failure (of hardware or software) in

 

 

the UPS internal control system. A second message may indicate internal test

 

 

or software timeout. The load has been automatically transferred to the Static

 

 

Bypass Line. Power to the load is not being conditioned by the UPS.

 

 

[Contact Liebert Customer Service and Support.]

 

 

Critical power supply failure

A failure has been detected in one of the low voltage power supplies. The load

 

 

has been automatically transferred to the Static Bypass Line. Power to the load

 

 

is not being conditioned by the UPS.

 

 

[Contact Liebert Customer Service and Support.]

 

 

Load transferred due to internal

A failure has been detected in the UPS. More specific information may be

protection

 

available in a separate Alarm Message. The load has been automatically

 

 

transferred to the Static Bypass Line (provided the power available on the

 

 

bypass line is within specifications). Power to the load is not being conditioned

 

 

by the UPS.

 

 

[Contact Liebert Customer Service and Support.]

 

 

 

64 Operation

Page 72
Image 72
Liebert Series 300 manual UPS System