GROUNDING | LOCAL | LOCAL | |
GROUNDING | |||
ELECTRODE | |||
GROUNDING | |||
ELECTRODE | |||
PER NEC | |||
ELECTRODE | |||
PER NEC | |||
| |||
| PER NEC | ||
|
| ||
GROUNDING |
| LOCAL | |
ELECTRODE |
| GROUNDING | |
PER NEC |
| ELECTRODE | |
|
| PER NEC |
Figure 5. Preferred Grounding Configuration with Ungrounded Delta Source Input (top) and
Corner-Grounded Delta (bottom)
7.5.Grounding Configuration, 480 or 600 VAC Input and Output, Delta Source or
As previously mentioned, Series 600T UPS modules require a bypass input neutral for sensing and monitoring. With a
If building service is ungrounded delta (and there is no intent to operate with one corner of the delta grounded, either on purpose or accidentally), the UPS requires the Series 600T Artificial Neutral Kit for proper operation. This kit uses a resistor network to create a reference point for the bypass input. In this case, the UPS output neutral must be bonded to the UPS ground. See Figure 5 above.
If the building service is
12 | Installation Manual |