Liebert Series 600T UPS, 65-225 kVA, Single Module 3
3. UNLOADING AND HANDLING
Because the weight distribution in each UPS and
ancillary cabinet is uneven, use extreme care
during handling and transport. Your installation
may also include Battery Cabinets, a Bypass
Transformer Cabinet and a Maintenance Bypass
Cabinet, Panelboard or Switchboard.
WARNING
EXERCISE EXTREME CARE WHEN
HANDLING UPS CABINETS TO AVOID
EQUIPMENT DAMAGE OR INJURY TO
PERSONNEL. THE UPS MODULE CAN
WEIGH UP TO TWO TONS. THE BATTERY
CABINETS WEIGH UP TO 5100 POUNDS.
THE UPS MODULES ARE HEAVIER IN
THE BACK THAN THE FRONT BECAUSE
OF THE WEIGHT OF THE MAGNETICS.
LOCATE CENTER OF GRAVITY SYMBOLS
BEFORE HANDLING CABINET. TEST LIFT
AND BALANCE THE CABINET BEFORE
TRANSPORTING. MAINTAIN MINIMUM
TILT FROM VERTICAL AT ALL TIMES.
WARNING
INTERNAL BATTERY CABINET
STRAPPING MUST BE VERIFIED BY
MANUFACTURER PRIOR TO MOVING
THIS UNIT.
THIS UNIT CONTAINS NON-SPILLABLE
BATTERIES. KEEP UNIT UPRIGHT. DO
NOT STACK. DO NOT TIP.
FAILURE TO HEED THIS WARNING
COULD RESULT IN SMOKE, FIRE OR
ELECTRICAL HAZARD. CALL 1-800-
LIEBERT PRIOR TO RELOCATING
BATTERY CABINET (AFTER INITIAL
INSTALLATION).
4. INSPECTIONS4.1. External Inspections
1. While the UPS system is still on the truck,
inspect the equipment and shipping
container(s) for any signs of damage or
mishandling. Do not attempt to install the
system if damage is apparent. If any damage is
noted, file a damage claim with the shipping
agency within 24 hours and contact Liebert
Global Services at 1-800-543-2378 to inform
them of the damage claim and the condition of
the equipment.
2. Locate the bag containing the keys for the front
access door. The bag is attached to the cabinet.
3. Compare the contents of the shipment with the
bill of lading. Report any missing items to the
carrier and to Liebert Global Services
immediately.
4. Check the nameplate on the cabinet to verify
that the model number corresponds with the
one specified. Record the model number and
serial number in the front of this installation
manual. A record of this information is
necessary should servicing become required.
4.2. Internal Inspections
1. Verify that all items have been received.
2. If spare parts were ordered, verify arrival.
3. Open doors and remove cabinet panels to check
for shipping damage to internal components.
4. Check for loose connections or unsecured
components in the cabinet(s).
5. Check for installation of circuit breaker line
safety shields. There should be no expos ed
circuit breaker terminals when the cabinet
doors are opened.
6. Remove any orange shipping braces or
brackets from the transformers.
7. Check for any unsafe condition that may be a
potential safety hazard.