GROUNDING |
ELECTRODE |
PER NEC |
Figure 4. Preferred Grounding Configuration, 208 VAC input and output
7.4.Preferred Grounding Configuration, 208 VAC Input and Output, Non- Isolated Load,
A few applications in this power range have 208 VAC input and output, and a connected load consisting of multiple Power Distribution Units (PDUs), panelboards, switchboards or other items of load equipment which do not have isolation transformers.
Notice in Figure 4 above that the UPS module main input and bypass input are connected to a
The UPS module output neutral and the load neutral are solidly connected to the building service neutral, which is bonded to the grounding conductor at the service entrance equipment.
This arrangement is typical for systems with 208 VAC input and output. However, it does not provide any isolation or
Liebert Series 600T UPS, | 11 |