Table 5

Example View Event Log Response

DATE

TIME

DESCRIPTION

 

 

 

 

 

10/21/97

16:34:39

Transferred to Preferred

 

10/21/97

16:34:39

Transfer Test Passed

 

10/21/97

16:34:39

Transferred to Alternate

 

10/21/97

16:34:38

Transfer Test Initiated

 

10/21/97

16:34:38

Alternate Source Available

 

09/27/97

07:22:11

In Sync

 

09/27/97

07:21:08

Out of Sync

 

06/01/97

02:10:32

Transferred to Preferred

 

06/01/97

02:10:29

Preferred Source Available

 

06/01/97

01:29:13

Transferred to Alternate

 

06/01/97

01:29:13

Preferred Source Fail

 

 

 

 

 

Logged Events include:

Preferred Source Fail Preferred Source Available Alternate Source Fail Alternate Source Available Out of Sync

In Sync

Peak Overload Peak Overload Gone Transfer Inhibit

OK to Transfer Power Supply Fault Power Supply OK Switch in Normal Mode Manual Transfer to S1 Manual Transfer to S2 Bypass to S1 Bypass to S2 Transferred to Alternate Transferred to Preferred Transfer Test Initiated Transfer Test Pended Transfer Test Passed Transfer Test Failed

Table 6

Example View Settings Response

CURRENT SETTINGS:

 

System Time:

10/21/97 16:23:54

Nominal Voltage:

120

Amps:

 

24

Frequency:

 

60

Phase:

 

1

Neutral:

 

YES

Unit Type:

 

UNDERFLOOR

Sync Window:

10

Auto Retransfer:

ENABLED

Retransfer Delay:

5

Current Inhibit:

5

Inhibit Type:

MANUAL

Transfer Test:

ENABLED

Next Test:

 

10/01/97 23:59:58

Test Interval:

90

Preferred Source

S1

 

 

 

Operating Instructions

13

Page 17
Image 17
Liebert SmartSwitchTM Example View Event Log Response, Example View Settings Response, Logged Events include