IMPORTANT SAFETY INSTRUCTIONS
!
!
!
WARNING
THERE ARE NO
NOTE
Read the entire User’s Manual before installing and operating the SmartSwitch. Adhere to all operating instructions and warnings on the unit and in this manual.
Liebert Corporation neither recommends nor knowingly sells this product for use with life support or other
The SmartSwitch is suitable for indoor use only. Protect unit from excessive moisture and install in an area free from flammable liquids, gases, or corrosive substances.
The unit is designed to operate from solidly grounded AC power sources only. Provide input overcurrent protection in accordance with the unit ratings. Wire and ground the unit according to national and local electrical safety codes.
CAUTION
The unit is supplied by two power sources. Unit may be electrically live if either of the two input sources is ON, even when the electronics module is removed. To isolate the unit, turn OFF and lock out BOTH input power sources.
CAUTION
If unit is furnished with input power plugs, the ground (earth) leakage current must not exceed 2.75 milliamperes. Most information technology equipment meets this requirement if no more than 4 pieces of equipment are powered from this unit. Note: These instructions may be modified by local wiring regulations.
! CAUTION
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. Operation of this unit in a residential area may cause harmful interference which the user must correct at his own expense.