Lifebreath 155MAX RX Model 95MAX, DIMENSIONS 95MAX inches mm, Performance, Engineering Data, Side

Models: 200MAX RX 155MAX RX 155ECM

1 36
Download 36 pages 8.13 Kb
Page 5
Image 5
Model 95MAX

Model 95MAX

ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE

The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.

MOTORS AND BLOWERS

Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. 120 VAC, .8 Amps.

FILTERS

Washable air filters in exhaust and supply air streams.

MOUNTING THE HRV

Four threaded inserts at corners of the cabinet designed to accept PVC rein- forced polyester straps that are supplied with the unit.

DEFROST

Recirculating defrost system.

CASE

Twenty gauge prepainted galvanized steel (G60) for superior corrosion resis- tance. Insulated to prevent exterior condensation.

Drain connections 2 - 1/2" (12 mm) OD.

CONTROLS

ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, Recirculation mode (on compatible units), (each mode has 5 speeds). Control pad can be removed from HRV and remotely mounted.

WEIGHT 52 lbs. (23.6 kg) Shipping Weight 56 lbs. (25.4 kg)

DIMENSIONS 95MAX inches (mm)

PERFORMANCE

HVI CERTIFIED

Net supply airflow in cfm (L/s) against external static pressure

E.S.P

(external static pressure)

[cfm (L/s)]

@ 0.1" (25 Pa)

 

95 (45)

@ 0.2" (50 Pa)

 

92 (43)

@ 0.3" (75 Pa

 

89 (42)

@ 0.4" (100 Pa)

 

83 (39)

@ 0.5" (125 Pa)

 

76 (36)

@ 0.6" (100 Pa)

 

71 (34)

 

 

Maximum Temperature Recovery

88%

 

 

 

Sensible Effectiveness

 

 

@ 64 cfm (30 L/s)

(CSA C439M)

87%

Sensible Efficiency

 

 

@ 64 cfm (30 L/s)

32°F (0°C)

74%

Sensible Efficiency

 

 

@ 64 cfm (30 L/s)

-13°F (-25°C)

68%

 

 

 

VAC @ 60HZ

 

120

 

 

 

WATTS / Low speed

 

60

 

 

 

WATTS / High speed

 

150

 

 

 

Amp rating

 

0.9

 

18.5"

 

 

(470 mm)

 

 

 

knockout for

 

 

side mounting of

 

 

EXHAUST return port

 

 

6" round collar

 

 

converted to oval

24.5"

(622mm)

Core

 

 

Removably

 

 

Heat Recovery

 

 

minimum

 

 

18 inches (459 mm)

 

 

required for

 

 

service access

 

 

Drain Pan

 

 

Drain spout

 

FRONT

SIDE

Hanging

straps (4)

Threaded inserts (4) at corners

18.5"

ENGINEERING DATA (470 mm) DIMENSIONS 95MAX inches (mm)

SUPPLY Fresh air from outside 5" round collar

SUPPLY Fresh air to building 6" round (conv. to oval) collar

16"

(406 mm)

TOP

EXHAUST

Stale Air

to outside

5" round collar

EXHAUST Return air from building

Choice of port location Knockouts on top and side of unit (use 1 only) 6" round (conv. to oval) collar supplied

OPTIONS

99-104 Digital Electronic Timer - 20/40/60 min.

99-109 Air Sentry™ Air Quality Monitor designed to accept remote-

ly mounted Control Pad

99-250 Ventilation Dehumidistat - Dehumidistat designed to accept remotely mounted Control Pad

99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”

(150 mm)

99-185 Weatherhoods, Two - 5” (125 mm) c/w 1/4” (6 mm) mesh screen

WARRANTY

Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.

All units conform to

CSA and UL standards.