Lifebreath 4TONDHW(T), 60DHW(T), 60VENTAC, 60DHWDF(T) Part D - Proving Required Water Flow, Table D

Models: 40DHWDF(T) 4TONVENTAC 60VENTAC 40VENTAC 60DHWH(T) 4TONDHW(T) 60DHW(T) 40DHWH(T) 60DHWDF(T) 40DHW(T)

1 42
Download 42 pages 60.95 Kb
Page 39
Image 39
PART D - PROVING REQUIRED WATER FLOW

PART D - PROVING REQUIRED WATER FLOW

D.1 Effective Length Calculation

 

 

Fitting

#

EL

Total EL

________________

_________ x ________ = ___________

________________

_________ x ________ = ___________

________________

_________ x ________ = ___________

________________

_________ x ________ = ___________

________________

_________ x ________ = ___________

________________

_________ x ________ = ___________

________________

_________ x ________ = ___________

Measured (Actual) Length

 

___________

Total Effective Length

 

 

___________

PUMP:

 

 

D.2

Water Flow Rate

________ US GPM

D.3

Max. Head Press. at Water Flow

________ ft of head

 

(from specs)

 

 

D.4

Pressure Drop of Water Coil

5

ft of head

D.5

Available Head Press.

________ ft of head

 

(D.3 - D.4)

 

 

D.6

Total Effective Length

________ eff. ft

 

(from D.1)

 

 

D.7

Head Loss /100 ft

________ per 100 ft

 

(D.5 x 100 D.6)

 

 

D.8

Pipe Diameter

________ in.

 

(Table D 2)

 

 

TABLE D 1

EQUIVALENT LENGTHS FOR COPPER PIPE FITTINGS (straight pipe in feet)

 

 

FITTING

 

EQUIVALENT

FITTING

EQUIVALENT

 

 

LENGTH

 

LENGTH

 

 

 

 

 

 

Gate / Ball Valve (open)

1

long sweep 90o elbow

2￿

 

Globe Valve (open)

23

45o elbow

1￿

 

Angle Valve (open)

12

180o close return

6￿

 

Check Valve (open)

6

standard tee (straight through)

2

 

 

 

 

 

 

Balance Valve

18

standard tee (90o turn)

5￿

 

Standard Elbow

3

contraction or enlargement

2

￿

 

 

 

 

 

 

TABLE D 2

HEAD LOSS PER 100 FEET OF EQUIVALENT LENGTH

 

 

 

1/2" inside diameter

5/8" inside diameter

3/4" inside diameter

1" inside diameter

 

 

 

 

 

FLOW

HEAD LOSS

HEAD LOSS

HEAD LOSS

HEAD LOSS

(US GPM)

(FT./100FT)

(FT./100FT)

(FT./100FT)

(FT./100FT.)

 

 

 

 

 

 

1

3

2

1

*

 

1.5

6

4

1

*

 

2

9

7

2

*

 

2.5

14

9

3

*

￿

3

19

13

4

1

￿

 

 

 

 

 

 

3.5

25

17

5

1

￿

 

 

 

 

 

 

4

32

22

6

1

￿

 

 

 

 

 

 

4.5

39

27

7

2

￿

 

 

 

 

 

 

5

*

33

9

2

 

 

 

 

 

 

 

6

*

45

12

3

￿

 

 

 

 

 

 

7

*

*

16

4

￿

 

 

 

 

 

 

8

*

*

21

5

￿

 

 

 

 

 

 

9

*

*

26

6

￿

 

 

 

 

 

 

10

*

*

31

8

 

 

 

 

 

 

 

39

Page 39
Image 39
Lifebreath 4TONDHW(T), 60DHW(T), 60VENTAC, 60DHWDF(T), 60DHWH(T), 40VENTAC Part D - Proving Required Water Flow, Table D