Lightolier 1101FEM Series installation instructions IS 1101FEM, Airport Road, Fall River, MA

Models: 1001FEM Series 1101FEM Series 1101FEL Series

1 4
Download 4 pages 52.4 Kb
Page 1
Image 1
INSTRUCTION SHEET NO.

READ AND UNDERSTAND THESE INSTRUCTIONS

INSTRUCTION SHEET NO.

BEFORE INSTALLING LUMINAIRE.

 

IS:1101FEM

installation. To prevent electric shock, turn off electricity at main power supply before proceeding.

 

This luminaire is intended for installation in accordance with the National Electrical Code and local regulations.

 

 

 

 

To assure full compliance with local codes and regulations, check with your local electrical inspector before

 

 

 

 

Retain these instructions for maintenance reference.

 

 

 

 

 

D1007

 

Page 1 of 4

INSTALLATION PROCEDURE FOR:

Lytecaster® 1001FEM, 1101FEM and 1101FEL Series Frame-In Kits with Emergency Backup

CAUTION: (RISK OF FIRE) THIS IS A NON-IC RATED FRAME-IN KIT.

DO NOT INSTALL INSULATION ABOVE OR WITHIN 3 INCHES (76mm) OF ANY PART OF LUMINAIRE.

CAUTION: USE ONLY WITH REFLECTOR TRIMS PROVIDED BY LIGHTOLIER. USE OF OTHER MANUFACTURER’S TRIMS

MAY VOID THE UNDERWRITERS LABORATORIES LISTING AND COULD CONSTITUTE A FIRE HAZARD.

CAUTION: BEFORE INSTALLING FRAME-IN KIT AND REFLECTOR TRIM, READ ALL MARKINGS ON FRAME-IN KIT AND

REFLECTOR TO DETERMINE LAMP WATTAGE AND TYPE APPLICABLE FOR YOUR INSTALLATION.

INSTALLATION INSTRUCTIONS FOR GRID CEILING APPLICATIONS

1PREPARATION: Cut appropriately sized hole in Ceiling Tile (by others) at the position desired and place Ceiling Tile in Grid (by others) (Figure A). Loosen Wing Nuts on Frame Clamps enough to allow free movement of Mounting Bars (Figure B).

*Lightolier offers a hole cutter (HC-356) that can be purchased separately to assist with quick, clean trim installations. In this case, follow the hole cutting directions supplied with HC-356.

APERTURE HOLE SIZE

1001FEM SERIES

5-1/4” (134mm) DIA

 

 

1101FEM SERIES

6-15/16” (176mm) DIA

 

 

1101FEL SERIES

6-15/16” (176mm) DIA

 

 

2POSITION LUMINAIRE FRAME: Place Luminaire Frame on top of Ceiling Tile and center the frame aperture on the Ceiling Tile hole cut in Step 1 so that the aperture wall extends into the Ceiling Tile. Orient the Luminaire Frame to align with the grid (Figure C). Grasp the T-Bar Clips on each end, one in each hand, lift the clips to the top of the adjustment slots in the End bracket, extend the End brackets to contact the Ceiling Grid, and drop each T-Bar Clip over the Grid (Figure D).

NOTE: When the Luminaire Frame is to be used with Wall Wash Trims make sure to orient the Luminaire Frame side indicated by a label on the frame towards the wall to be illuminated.

3CLAMP TO GRID and LOCK LUMINAIRE FRAME: Making certain that the Luminaire Frame is still centered on the Ceiling Tile, tighten the T-Bar Clip Wing Nuts to attach the frame to the Ceiling Grid (Figure E). Retighten the Wing Nuts on the Frame Lock Clamps after the frame is positioned satisfactorily and is locked to the Ceiling Grid.

Figure A

Figure C

Figure E

 

 

 

Figure B

Figure D

Figure F

*BALLAST REPLACEMENT: Ballast replacement must be performed by a “qualified electrician”. TURN OFF POWER. Remove reflector trim from luminaire. Remove j-box cover nearest the ceiling opening to which the ballast is mounted by lifting the spring. Remove ballast assembly through the ceiling hole. Disconnect all input wiring to the ballast. Release all wires from ballast wire connectors by inserting small blade tool, with insulated handle, into wire release slots (Figure F). Remove ballast from j-box door and replace with new ballast. Rewire and reassemble.

*REFLECTOR TRIM INSTALLATION: See separate Trim Instruction Sheet for installation procedure.

IS:1101FEMA A  COMPANY631 Airport Road, Fall River, MA 02720Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background COMPANY

631 Airport Road, Fall River, MA 02720

Page 1
Image 1
Lightolier 1101FEM Series installation instructions IS 1101FEM, Airport Road, Fall River, MA, Instruction Sheet No