4SMART TOUCH control module (continued)
A blank message box is located on the Details Screen. This box will display various messages detailing the status of the control module. If a message is present in this box, the DETAILS button on the Status Screen will contain a yellow triangle with an exclamation mark (!) inside.
Displayed items are as follows:
•Delta T Shutdown - The temperature rise between the inlet and outlet temperatures has exceeded 55°F. Reference the SYNC Service Manual for more information regarding this shutdown.
•Outlet Temp Shutdown - The outlet temperature has exceeded 195°F. Reference the SYNC Service Manual for more information regarding this shutdown.
•Flue Temp Shutdown - The flue temperature has
exceeded 240°F. Reference the SYNC Service Manual for more information regarding this shutdown.
•Voltage too Low - The 120 VAC input to the control has dropped below 80 VAC. Reference the SYNC Service Manual for more information regarding this fault message.
•Connect System Sensor - System sensor is not detected by the Module 1 Control Module. For proper operation of the SYNC boiler the system sensor must be connected.
•Manual Shutdown - The boiler has been shutdown with the ON/OFF button on the Status Screen.