1 Determine boiler location (continued)

4.If a single combustion air opening is provided to bring combustion air in directly from the outdoors, the opening must be sized based on a minimum free area of one square inch per 3000 Btu/hr (7 cm2 per kW). This opening must be located within 12” (30 cm) of the top of the enclosure (see FIG. 1-7).

Combustion air requirements are based on the latest edition of the National Fuel Gas Code, NFPA 54 / ANSI Z223.1; in Canada refer to the latest edition of CGA Standard CAN/CSA B149.1. Check all local code requirements for combustion air. All dimensions based on net free area in square inches. Metal louvers or screens reduce the free area of a combustion air opening a minimum of approximately 25%. Check with louver manufacturers for exact net free area of louvers.

Where two openings are provided, one must be within 12" (30 cm) of the ceiling and one must be within 12" (30 cm) of the floor of the equipment room. Each opening must have a net free area as specified in Table 1B. Single openings shall commence within 12" (30 cm) of the ceiling. The minimum dimension of air openings shall not be less than 3" (80 mm).

￿CAUTION Under no circumstances should the equipment room ever be under negative

pressure. Particular care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may take away air from the unit.

The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the appliance. Common corrosive chemical fumes which must be avoided are fluorocarbons and other halogenated compounds, most commonly present as refrigerants or solvents, such as Freon, trichlorethylene, perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the stainless steel heat exchanger, headers, flue collectors, and the vent system.

The result is improper combustion and a non-warrantable, premature appliance failure.

EXHAUST FANS: Any fan or equipment which exhausts air from the equipment room may deplete the combustion air supply and/or cause a downdraft in the venting system. Spillage of flue products from the venting system into an occupied living space can cause a very hazardous condition that must be corrected immediately.

TABLE - 1B

MINIMUM RECOMMENDED COMBUSTION

AIR SUPPLY TO EQUIPMENT ROOM

 

FIG. 1-4

FIG. 1-5

 

 

FIG. 1-6

 

FIG. 1-7

 

*Outside Air from

*Outside Air from

 

Inside Air from

 

 

 

2 Ducts Delivered from Interior Space2

*Outside Air from

Model

2 Openings Directly from

2 Ducts Delivered from

 

 

 

 

Number

Outdoors1

Outdoors1

Same Story

Different

1 Opening Directly

 

 

 

 

 

2

 

 

 

 

 

 

 

 

Stories

from Outdoors, in

 

 

 

 

 

 

 

 

(cm2)1

 

 

 

 

 

 

 

 

 

 

Top

Bottom

Top

Bottom

Top

 

Bottom

Total

 

 

 

 

Opening, in2

Opening, in2

Opening, in2

Opening, in2

Opening, in2

 

Opening, in2

Opening, in2

 

 

(cm2)

(cm2)

(cm2)

(cm2)

(cm2)

 

(cm2)

(cm2)

 

FB 1500

375

375

750

750

1500

 

1500

3000

500

(2420)

(2420)

(4839)

(4839)

(9678)

 

(9678)

(19355)

(3226)

 

 

FB 2000

500

500

1000

1000

2000

 

2000

4000

667

(3226)

(3226)

(6452)

(6452)

(12904)

 

(12904)

(25807)

(4304)

 

 

FB 2500

625

625

1250

1250

2500

 

2500

5000

833

(4033)

(4033)

(8065)

(8065)

(16129)

 

(16129)

(32258)

(5381)

 

 

FB 3000

750

750

1500

1500

3000

 

3000

6000

1000

(4839)

(4839)

(9678)

(9678)

(19355)

 

(19355)

(38710)

(6452)

 

 

FB 3500

875

875

1750

1750

3500

 

3500

7000

1167

(5646)

(5646)

(11291)

(11291)

(22581)

 

(22581)

(45162)

(7530)

 

 

The above requirements are for the appliance only; additional gas fired appliances in the equipment room will require an increase in the net free area and/or volume to supply adequate combustion air for all appliances.

No combustion air openings are needed when the appliance is installed in a space with a volume NO LESS than 50 cubic feet per 1,000 Btu/hr of all installed gas fired appliances. Buildings MUST NOT be of *“Tight Construction”3.

1Outside air openings shall directly communicate with the outdoors.

2Combined interior space must be 50 cubic feet per 1,000 Btu/hr input. Buildings MUST NOT be of *“Tight Construction”.

3”Tight Construction” is defined as a building with less than 0.40 ACH (air changes per hour). For buildings of “Tight Construction”, provide air openings into the building from outside.

13

Page 13
Image 13
Lochinvar 3.5, 2.5 service manual Minimum Recommended Combustion AIR Supply to Equipment Room

3, 2, 3.5, 2.5 specifications

The Lochinvar 2, 3, 3.5, and 2.5 models are a standout lineup in the realm of commercial and residential water heating solutions. Known for their advanced technology and high efficiency, these units cater to a wide range of applications, ensuring optimal performance and reliability.

One of the key features of the Lochinvar models is their robust construction. Each unit is designed to withstand rigorous operational demands while providing excellent thermal efficiency. They are equipped with stainless steel heat exchangers, which offer superior resistance to corrosion and extend the lifespan of the equipment. This durability is essential for both commercial and residential settings where demand can vary significantly.

The Lochinvar 2, 3, 3.5, and 2.5 models utilize innovative control systems that enhance their operational efficiency and user convenience. The built-in Smart Control technology allows for easy monitoring and adjusting of system parameters, ensuring that users can maintain optimal performance with minimal effort. This feature is especially beneficial in commercial settings where large volumes of hot water are required, as it enables users to effectively manage their energy consumption.

Energy efficiency is another hallmark of the Lochinvar lineup. With high-efficiency ratings, these models help reduce energy costs significantly, making them an environmentally friendly option for heating water. The use of advanced combustion technology ensures that these units can deliver maximum heat output with minimal fuel consumption.

Additionally, the Lochinvar models are designed with safety and reliability in mind. They feature multiple safety controls and diagnostics that alert users to potential issues before they escalate, providing peace of mind. The integration of advanced venting options allows for flexible installation configurations, accommodating various building layouts and space requirements.

In summary, the Lochinvar 2, 3, 3.5, and 2.5 models define modern water heating technology with their combination of durability, efficiency, and advanced features. With their innovative design and user-friendly controls, they meet the demanding needs of both commercial and residential users, making them a top choice in the water heater market. Whether for new installations or replacements, these units deliver reliable performance and value.