1Service

Sequence of operation (continued)

Table 1A (continued from previous page) Sequence of operation - space heating and DHW

 

OPERATION

DISPLAY

 

 

8. If the boiler is not part of a cascade, and the DHW call for heat

 

 

remains active for more than 30 minutes, and the space heating

 

 

call for heat is also active, then the control will turn on the boiler

BLR: SH 41% RATE

 

pump, turn off the DHW pump after 2 seconds, and resume

 

modulating based on the space heating set point. As long as

OUT: 123.0F(129)

 

both the space heating and DHW calls for heat remain active,

 

 

 

the control will switch back and forth between the two modes

 

 

until one of them is satisfied.

 

 

 

9. Once both calls for heat are satisfied, the control will turn off the

BLR: POSTPURGE

 

burner. The blower will remain on for the 10 second postpurge

 

cycle. Any pumps that are running will continue to run for their

OUT: 127.4F(129)

 

respective pump delay times, then turn off.

 

 

 

10.

Boiler pump off, system pump continues its delay if longer.

BLR: Standby

 

 

OUT: 124.7F(129)

11.

System pump off.

BLR: Standby

 

 

OUT: 122.9F(129)