1Service (continued)

Figure 1-1Outdoor Air Reset Curve

 

 

WATER

 

 

TEMPERATURE

 

 

SET POINT

 

 

MAXIMUM

 

 

RESET

 

 

Default = 180°F

 

 

USER

 

 

SET POINT

 

 

Default = 125°F

 

 

MINIMUM

 

 

RESET

 

 

Default = 70°F

 

 

Default = 25°F

Default = 70°F

OUTDOOR

 

OUTDOOR AIR

 

AT MINIMUM RESET

TEMPERATURE

OUTDOOR AIR

 

AT MAXIMUM RESET

 

Maximum air temperature

When the outdoor air temperature rises to or above this point, the water temperature will be at its minimum setting (FIG. 1-1). This parameter can be changed by the installer by accessing parameter F2. The temperature range of this parameter is -30°F (-34°C) to 90°F (32°C). The default value is 70°F (21°C).

Maximum SH set point

When the outdoor temperature drops below its minimum setting (F1) the water temperature will be at this point, if the SH set point is set higher (FIG. 1-1). This parameter can be changed by the installer by accessing parameter F3. The temperature range of this parameter is 0°F (-18°C) to 190°F (88°C). The default value is 180°F (82°C).

Minimum SH set point

When the outdoor temperature rises to or above its maximum setting (F2) the water temperature will be at this point (FIG. 1-1). This parameter can be changed by the installer by accessing parameter F4. The temperature range of this parameter is 0°F (-18°C) to 190°F (88°C). The default value is 70°F (21°C).

Outdoor air shutdown

When the outdoor temperature rises above this point, the control will block all SH demands (DHW demands will still be active). This parameter can be changed by the user or the installer by accessing parameter F5. The temperature range of this parameter is 0°F (-18°C) to 120°F (49°C). The default value is 70°F (21°C).

Outdoor air shutdown differential

The outdoor air shutdown differential parameter is the number of degrees below parameter F5 the outdoor air temperature must go before the boiler will respond to a SH demand. This parameter can be changed by the user or the installer by accessing parameter F6. The temperature range of this parameter is 0°F (0°) to 90°F (50°C). The default value is 10°F (5°C).

Shift reset curve

The shift reset curve parameter shifts the actual set point above the calculated set point the number of degrees in this parameter. This parameter can be changed by the installer by accessing parameter F7. The temperature range of this parameter is -27°F (-15°C) to 27°F (15°C). The default value is 0°F (0°C). This feature will be active if this parameter is set to anything other than 0°F (0°C).

19

Page 19
Image 19
Lochinvar 399 - 800 Maximum air temperature, Maximum SH set point, Minimum SH set point, Outdoor air shutdown

399 - 800 specifications

Lochinvar is known for its cutting-edge water heating and boiler systems, and the Lochinvar 399 - 800 series is no exception. Specifically designed for commercial applications, this series brings advanced technology and engineering to the forefront of hydronic heating solutions.

One of the standout features of the Lochinvar 399 - 800 series is its impressive efficiency. Equipped with a condensing design, these boilers utilize high-efficiency stainless steel heat exchangers that allow for maximum heat transfer while minimizing energy consumption. With an impressive thermal efficiency of up to 96%, the Lochinvar 399 - 800 series stands out in its class, offering significant energy savings and reduced operational costs over time.

Another key characteristic of this series is its robust construction. Designed with longevity in mind, the boilers are built using high-quality materials that withstand extreme temperatures and pressures. The stainless steel design not only enhances durability but also combats corrosion, ensuring a long service life and reduced maintenance costs for users.

The Lochinvar 399 - 800 series also incorporates advanced control technologies. With its intuitive control system, users can easily adjust and monitor heating parameters, ensuring optimal performance and comfort. The integrated Control Wizard feature simplifies the setup process, allowing for quick commissioning and troubleshooting. Additionally, the optional Lochinvar SMART CONTROL technology provides remote monitoring capabilities, allowing operators to keep track of system performance from anywhere.

Versatility is another hallmark of the Lochinvar 399 - 800 series. These boilers come in a range of sizes, with the ability to modulate output based on real-time heating demands. This flexibility ensures that systems can operate efficiently under varying load conditions, making them ideal for schools, hospitals, and commercial buildings requiring consistent hot water availability.

In summary, the Lochinvar 399 - 800 series exemplifies modern boiler technology, combining energy efficiency, durability, advanced controls, and versatility. As businesses and facilities seek to enhance their heating systems, the Lochinvar 399 - 800 offers a reliable and forward-thinking solution for today's energy-conscious environment. Investing in this state-of-the-art boiler system not only improves comfort but also fosters sustainability and cost-effectiveness in commercial heating applications.