Lochinvar 502 - 2072, 402 - 2072 service manual Maintenance continued, B Net Manifold Pressure

Models: 502 - 2072 402 - 2072

1 44
Download 44 pages 8.33 Kb
Page 29
Image 29
TABLE 2B

Copper-fin II/IIE Boiler, Water Heater and Pool Service Manual

2 Maintenance (continued)

Figure 2-4_Measuring manifold gas pressure

 

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

REGULATOR

 

 

 

CHAMBER

 

 

 

ADJUSTMENT

 

 

 

MANIFOLD

 

 

 

PRESSURE

(UNDER CAP

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

SCREW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INLET

TEE

OUTLET

 

MANOMETER

 

GAS

 

 

 

TO BARBED

 

 

 

 

 

 

 

VALVE

 

FITTING

 

 

CONTROL

 

 

 

 

KNOB

 

 

TABLE 2B

Net Manifold Pressure

Regulator Pressure Less

Front Chamber Pressure

MODEL

Nat. Gas

LP

402 - 752

1.8'' w.c.

4.6’’ w.c.

992 - 2072

1.2'' w.c.

4.6’’ w.c.

Regulator Pressure Less 29 Manual background