F:Outdoor air reset (boiler only)

Outdoor air reset operation

When the outdoor air sensor is installed, the control will calculate the water temperature set point based on the outdoor air temperature. As the outdoor air temperature drops, the water temperature set point increases. This feature allows the unit to be more efficient in periods of mild weather, see FIG. 1-1 on page 17.

F1: Minimum air temperature

When the outdoor air temperature drops to this point, the water temperature will be at its maximum setting (FIG. 1-1). The set point will continue to increase as the outdoor temperature drops below this setting. The water temperature will be limited by the user set point. This parameter can be changed by the installer by accessing parameter F1. The temperature range of this parameter is -22°F (-30°C) to 86°F (30°C). The default value is 25°F (-4°C).

F2: Maximum air temperature

When the outdoor air temperature rises to or above this point, the water temperature will be at its minimum setting (FIG. 1-1). This parameter can be changed by the installer by accessing parameter F2. The temperature range of this parameter is -22°F (-30°C) to 86°F (30°C). The default value is 70°F (21°C).

F3: Maximum SH set point

When the outdoor temperature drops to its minimum setting (F1) the water temperature set point will be at this value, if the SH set point is set higher (FIG. 1-1). This parameter can be changed by the installer by accessing parameter F3. The temperature range of this parameter is 32°F (0°C) to 248°F (120°C). The default value is 180°F (82°C).

F4: Minimum SH set point

When the outdoor temperature rises to or above its maximum setting (F2) the water temperature will be at this value (FIG. 1-1). This parameter can be changed by the installer by accessing parameter F4. The temperature range of this parameter is 32°F (0°C) to 248°F (120°C). The default value is 70°F (21°C).

F5: Outdoor air shutdown

When the outdoor temperature rises above this point, the control will block all SH demands (DHW demands will still be active). This parameter can be changed by the user or the installer by accessing parameter F5. The temperature range of this parameter is 32°F (0°C) to 122°F (50°C). The default value is 80°F (27°C).

F:Outdoor air reset (boiler only) 18 Outdoor air reset operation