Lochinvar 402 - 2072 Fault, Cause, Corrective Action, Troubleshooting, No Display, No Burner

Models: 502 - 2072 402 - 2072

1 44
Download 44 pages 8.33 Kb
Page 32
Image 32
Table 3A Troubleshooting Chart - No Display

Copper-fin II/IIE Boiler, Water Heater and Pool Service Manual

3 Troubleshooting

Table 3A Troubleshooting Chart - No Display

FAULT

CAUSE

 

 

CORRECTIVE ACTION

 

 

 

 

 

 

 

 

 

 

Check external line switch, fuse, or breaker.

 

 

 

 

• Check position of ON/OFF switch. Turn switch to the

 

- No 120 VAC supplied to unit.

 

ON position.

 

 

 

 

 

 

 

 

 

 

 

• Check 120 VAC

through

the

ON/OFF switch.

No

 

 

 

voltage through switch, replace switch.

 

 

 

 

 

No Display

 

• Check wiring harness connection between the display

- Bad wiring connection.

 

board and the main control board. Connect the harness

 

 

 

at both points.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Blown fuse.

Replace

fuse

F6

on

the

main

control board,

see

 

 

FIG. 3-1 on page 31 of this manual.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Bad display board.

Replace board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Bad main control board.

Replace main control board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Main control board temperature set point

Review temperature setting.

 

 

 

 

 

 

satisfied.

 

 

 

 

 

 

 

 

 

 

 

 

 

- Remote thermostat satisfied.

Review remote thermostat setting.

 

 

 

 

No Burner

 

 

 

 

 

 

 

 

 

 

 

 

 

- Outside air temperature above Warm

Check

location

of

outside

air

sensor.

Check

Operation

 

Weather Shutdown (WWSD) set point for

 

resistance of outdoor air sensor and compare to Table

 

main control board.

 

3D on page 33 of this manual.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Unit locked out on fault.

Consult

display for

specific

fault.

Refer

to

fault

 

 

descriptions on pages 35 - 42 of this manual for

 

 

 

 

 

 

corrective actions.

 

 

 

 

 

 

 

 

 

 

 

 

- Ramp delay active.

• Check ramp delay parameter settings. Optional PC

 

 

software required.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Does Not

 

Turn ramp delay

feature

off.

See

page 18

of

this

 

 

manual for instructions on how to turn this feature off.

Modulate to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100%

- Boiler controlled by BMS.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Check

BMS

parameter

settings.

Optional

PC

 

- Outlet temperature too high.

 

 

software required.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Delta T too high.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT 32 CAUSE

Page 32
Image 32
Lochinvar 402 - 2072 Fault, Cause, Corrective Action, A Troubleshooting Chart - No Display, No Burner, Operation, 100%