3 Troubleshooting
Table 3A Troubleshooting Chart - No Display
FAULT | CAUSE |
|
| CORRECTIVE ACTION |
|
| ||||||||
|
|
|
|
|
| |||||||||
|
| • | Check external line switch, fuse, or breaker. |
|
| |||||||||
|
| • Check position of ON/OFF switch. Turn switch to the | ||||||||||||
| - No 120 VAC supplied to unit. |
| ON position. |
|
|
|
|
|
|
|
|
| ||
|
| • Check 120 VAC | through | the | ON/OFF switch. | No | ||||||||
|
|
| voltage through switch, replace switch. |
|
| |||||||||
|
|
| ||||||||||||
No Display |
| • Check wiring harness connection between the display | ||||||||||||
- Bad wiring connection. |
| board and the main control board. Connect the harness | ||||||||||||
|
|
| at both points. |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| ||||
| - Blown fuse. | • | Replace | fuse | F6 | on | the | main | control board, | see | ||||
|
| FIG. |
|
|
| |||||||||
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| - Bad display board. | • | Replace board. |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| ||||||
| - Bad main control board. | • | Replace main control board. |
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| ||||||
| - Main control board temperature set point | • | Review temperature setting. |
|
|
|
|
| ||||||
| satisfied. |
|
|
|
|
|
|
|
|
|
|
|
| |
| - Remote thermostat satisfied. | • | Review remote thermostat setting. |
|
|
|
| |||||||
No Burner |
|
|
|
|
|
|
|
|
|
|
|
|
| |
- Outside air temperature above Warm | • | Check | location | of | outside | air | sensor. | Check | ||||||
Operation | ||||||||||||||
| Weather Shutdown (WWSD) set point for |
| resistance of outdoor air sensor and compare to Table | |||||||||||
| main control board. |
| 3D on page 33 of this manual. |
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
| |||||
| - Unit locked out on fault. | • | Consult | display for | specific | fault. | Refer | to | fault | |||||
|
| descriptions on pages 35 - 42 of this manual for | ||||||||||||
|
|
| ||||||||||||
|
|
| corrective actions. |
|
|
|
|
|
|
|
| |||
|
|
| ||||||||||||
| - Ramp delay active. | • Check ramp delay parameter settings. Optional PC | ||||||||||||
|
| software required. |
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |||||
Unit Does Not |
| • | Turn ramp delay | feature | off. | See | page 18 | of | this | |||||
|
| manual for instructions on how to turn this feature off. | ||||||||||||
Modulate to |
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
100% | - Boiler controlled by BMS. |
|
|
|
|
|
|
|
|
|
|
|
| |
|
| • Check | BMS | parameter | settings. | Optional | PC | |||||||
| - Outlet temperature too high. | |||||||||||||
|
| software required. |
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| ||||
| - Delta T too high. |
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
32