Lochinvar 45000, 260000 service manual Heat Exchanger Pressure Drop Chart, Water Connections

Models: 45000 260000

1 52
Download 52 pages 10.43 Kb
Page 26
Image 26

4Water connections

Hot water piping must be supported by suitable hangers or floor stands, NOT by the boiler. Copper pipe systems will be subject to considerable expansion and contraction. Rigid pipe hangers could allow the pipe to slide in the hanger resulting in noise transmitted into the system. Padding is recommended on rigid hangers installed with a copper system. The boiler pressure relief valve must be piped to a suitable floor drain. See the relief valve section on page 23 of this manual.

CAUTION

A leak in a boiler system will cause the

system to intake fresh water constantly,

 

 

which will cause the tubes to accumulate

 

a lime/scale build up. This will cause a

 

NON-WARRANTABLE FAILURE.

Water Connections

Heating Boilers with inputs of 45,000 - 260,000 Btu/hr have 1 1/2" NPT inlet and outlet connections.

CAUTION Field installed reducing bushings may decrease flow resulting in boiler noise or

flashing to steam.

Installation & Service Manual

Circulator Pump Requirements

This is a low mass, high efficiency hot water boiler which must have adequate flow for quiet, efficient operation. The boiler circulating pump must be field supplied. The boiler circulator pump must operate continuously while the boiler is firing. Pump selection is critical to achieve proper operation. A pump should be selected to achieve proper system design water temperature rise. A heat exchanger pressure drop chart (Table 4C) is provided to assist in proper pump selection. Also provided is a System Temperature Rise Chart (Table 4B on page 25). This table provides GPM and boiler head-loss at various temperature rises for each boiler based on Btu/hr input. Temperature rise is the difference in boiler inlet temperature and boiler outlet temperature while the boiler is firing. Example: The boiler inlet temperature is 160°F and the boiler outlet temperature is 180°F, this means that there is a 20°F temperature rise across the boiler.

TABLE - 4C

HEAT EXCHANGER PRESSURE DROP CHART

FT/HD

26

6

5

4

3

2

1

0

0

5

10

15

20

25

30

35

 

 

 

Gallons per Minute

 

 

 

CB 45

CB 75

CB 90

CB 135

CB 180

CB 215 CB 260

Page 26
Image 26
Lochinvar 45000, 260000 service manual Heat Exchanger Pressure Drop Chart, Water Connections, Circulator Pump Requirements