Installation & Service Manual
8Troubleshooting
Troubleshooting Guide: M9 Solution Boilers
Step 1: | Is the spark | ||
| ignitor sparking? | ||
|
|
|
|
|
|
|
|
|
| Yes |
|
|
|
|
|
Step 2: | Is the pilot | |
staying on? | ||
| ||
|
|
Yes
|
|
|
| Check continuity on the spark |
|
| Check for an open | ||||||||
| No |
| cable. Check for 24 VAC on |
|
| sensor. If no open | |||||||||
|
| the 24v terminal (gray wire) |
|
| sensor, make sure | ||||||||||
|
|
|
|
|
| ||||||||||
|
|
| |||||||||||||
|
|
|
| on the ignition module. |
|
| there’s a call for | ||||||||
|
|
|
|
|
|
|
|
|
|
|
| heat. If call for heat | |||
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| is present, replace | |||
|
|
|
|
|
|
|
|
|
|
|
| temperature control. | |||
|
|
|
|
|
| No |
|
| Yes |
|
| ||||
|
|
| Check the pilot |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| tube for gas. |
|
|
|
|
|
|
|
|
|
|
| |
No |
|
| Check draft. |
|
|
|
|
|
|
|
|
|
| ||
|
| Replace ignition |
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| module. |
|
| No |
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Is there 24 VAC (purple wire) on the
Step 3: Is the gas valve getting 24 VAC
to the MV terminal?
Yes
|
| Replace the | |
No | |||
| ignition | ||
|
| ||
|
| module. | |
|
|
|
Check gas pressure and make sure gas valve knob is on.
Yes
No
Is there 24 VAC (tan wire) on the
Yes
No
Check voltage to and from the transformer.
No
Check incoming 120 VAC.
Check 24 VAC at R and W on the terminal strip.
Yes
Check each of the following for an open:
If any of these devices are open, press the reset button.
Check each of the following for an open:
-X and B on the terminal strip
49