Installation & Service Manual
5Electrical connections
Maximum Set Point Determination
The maximum set point for the control is factory set. Boilers can be set to 240°F max.
These maximum set points are established by cutting the OJ1 and OJ2 jumpers located on the right side of the temperature controller. The maximum set point is determined as shown below in Table 5C.
TABLE - 5C
MAXIMUM SET POINT DETERMINATION
| OJ1 | OJ2 | MAX. |
|
| SET POINT |
| ||
|
|
|
| |
|
|
|
|
|
| Connected | Connected | 240°F |
|
|
|
|
|
|
| Cut | Connected | 190°F |
|
|
|
|
|
|
| Connected | Cut | 200°F |
|
|
|
|
|
|
| Cut | Cut | 160°F |
|
|
|
|
|
|
| Anytime that OJ1 is the only jumper cut, a | |
NOTICE | ||
new overlay is required under the Set | ||
| ||
| Point knob on the temperature controller | |
| because the scale has changed to a | |
| maximum of 190°F. |
Anytime the OJ2 jumper is cut (with or without OJ1), a new overlay is required under the Set Point knob on the temperature controller because the scale has changed to a maximum of 200°F.
Set Point
The Set Point knob specifies the target inlet water temperature in degrees, Fahrenheit. After the water temperature reaches the set point, the temperature control shuts off the burners.
Differential
The Differential specifies the number of degrees below the set point that the control will allow the water temperature to drop before it brings the unit back on again.
High-Fire Offset
The temperature control operates a
The
The
If the High Fire Offset knob is set to 0 or 1, the delay will be 10 seconds; if set to 2 or above the delay will be 120 seconds.
Boiler Application
Standard boiler units are equipped with one inlet water temperature sensor. A system sensor is also provided for use as a remote system sensor. Boilers with the outdoor air reset option also have an outside air temperature sensor.
Temperature Control Sensors
This is a
1.Inlet Water Temperature Sensor
2.System Sensor
3.Outside Air Temperature Sensor
Inlet Water Temperature Sensor
This sensor measures the inlet water temperature coming into the unit.
The inlet water temperature sensor is placed into the inlet bulbwell on the boiler. This sensor is installed by the factory in new units.
System Sensor
Depending upon how your unit is set up, this sensor can be used as a system sensor in a boiler system or a tank sensor for water heater applications. Connect this sensor to the SYS/TANK contacts on the control board.
36