Lochinvar Hot Water Generator 5Troubleshooting, Symptom, Probable Cause, Corrective Action

Models: Hot Water Generator

1 24
Download 24 pages 52.64 Kb
Page 12
Image 12
5Troubleshooting

Hot Water Generator Installation and Operation Manual

5Troubleshooting

SYMPTOM

PROBABLE CAUSE

 

 

CORRECTIVE ACTION

 

 

Water heater

does not

• The

thermometer

is

not

correctly

• Check

the

 

water

 

temperature

 

with

a

maintain the

required

sensing the water temperature.

 

 

 

temperature gauge that is known to be

 

 

 

 

 

 

 

 

 

temperature at the rated

 

 

 

 

 

 

 

 

 

correct.

Replace

the

thermometer

if

it

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

capacity.

 

 

 

 

 

 

 

 

 

 

is found to

be

incorrectly sensing

the

 

 

 

 

 

 

 

 

 

 

water temperature.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Inlet

energy

source pressure

is

too

• Check

the

primary

energy

 

source

 

 

low or boiler water temperature is too

pressure/temperature.

If

the reading

is

 

 

low.

 

 

 

 

 

 

 

 

low, adjust the inlet pressure/temperature to

 

 

 

 

 

 

 

 

 

 

 

meet the design requirements. If there is a

 

 

 

 

 

 

 

 

 

 

 

restriction in the primary energy source

 

 

 

 

 

 

 

 

 

 

 

line, the pressure reading will drop

 

 

 

 

 

 

 

 

 

 

 

excessively

 

when

 

the

generator

calls

 

 

 

 

 

 

 

 

 

 

 

for full energy on steam systems, even

 

 

 

 

 

 

 

 

 

 

 

though the pressure seems to be

 

 

 

 

 

 

 

 

 

 

 

normal during light demand. If the

 

 

 

 

 

 

 

 

 

 

 

primary pressure is correct, the system

 

 

 

 

 

 

 

 

 

 

 

should

reach

design

pressure

 

for

 

 

 

 

 

 

 

 

 

 

 

energy source in the tube bundle as the

 

 

 

 

 

 

 

 

 

 

 

temperature of the water in the tank

 

 

 

 

 

 

 

 

 

 

 

heater approaches shutoff.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Reconfigure

the

 

condensate

/

water

 

 

• The condensate / water return piping

return piping

and check valve to allow

 

 

has

not

been

installed

properly,

for

proper

drainage.

Check to

assure

 

 

allowing the condensate / water to

that there is no restriction in the

 

 

drain

freely

(by

gravity);

 

the

condensate

/

water

drain

line.

Replace

 

 

condensate / water drain line is

the check valve if it is leaking or has

 

 

restricted; or the condensate / water

failed.

Also,

check to assure that there

 

 

check valve is leaking or has failed.

 

 

is no restriction in the condensate /

 

 

 

 

 

 

 

 

 

 

 

water drain line.

 

 

 

 

 

 

 

 

 

 

 

• Water

bypass valve has not been

• Adjust bypass valve approximately half

 

 

adjusted (boiler water).

 

 

 

 

closed. Readjust as necessary.

 

 

 

 

 

 

• Control valve bulb not installed or not

• Notify factory for replacement.

 

 

 

 

 

 

properly installed in tank bulbwell.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Control valve actuator defective.

 

 

 

• Verify actuator is not working. Notify factory

 

 

 

 

 

 

 

 

 

 

 

for replacement.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outlet temperature is too

• The

thermometer

is

not

correctly

• Check the water temperature with a

high.

 

sensing the water temperature.

 

 

 

temperature gauge that is known to be

 

 

 

 

 

 

 

 

 

 

 

correct.

Replace

the

thermometer

if

it

 

 

 

 

 

 

 

 

 

 

 

is found to be incorrectly sensing the

 

 

 

 

 

 

 

 

 

 

 

water temperature.

 

 

 

 

 

 

 

 

 

 

• The condensate / water return piping

• Reconfigure

the

 

condensate

/

water

 

 

has

not

been

installed

properly,

return piping

and

check

valve

to allow

 

 

 

 

 

 

 

 

 

 

 

 

 

allowing the

condensate /

water

to

for

proper

drainage.

Check to

assure

 

 

 

 

 

 

 

 

 

 

 

 

 

drain

freely

(by

gravity);

 

the

that

there

 

is

no

restriction

 

in

the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

condensate

/

water

drain

line

is

condensate

/

water

drain

line.

Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

restricted;

or

the

condensate

/

water

the

check

valve

if

 

it is

leaking

 

or

has

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

check valve is leaking or has failed.

 

 

failed. Also, check to assure that there

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is no restriction in the condensate /

 

 

 

 

 

 

 

 

 

 

 

water drain line.

 

 

 

 

 

 

 

 

 

 

 

• Control valve bulb not installed or not

• Verify bulb is installed in bulbwell.

 

 

 

 

 

 

properly installed in tank bulbwell.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Control valve actuator defective.

 

 

 

• Verify actuator is not working. Notify factory

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for replacement.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SYMPTOM 12 PROBABLE CAUSE

Page 12
Image 12
Lochinvar Hot Water Generator operation manual 5Troubleshooting, Symptom, Probable Cause, Corrective Action