Lochinvar Hot Water Generator 2Installation continued, Examining the unit, Mounting the unit

Models: Hot Water Generator

1 24
Download 24 pages 52.64 Kb
Page 7
Image 7
2Installation (continued)

Hot Water Generator Installation and Operation Manual

2Installation (continued)

Examining the unit

After the unit has been set in place and uncrated, it should be carefully examined to assure that neither the main unit nor components have been damaged during shipping. If any evidence of damage is detected that could affect the safe operation of the unit, contact Lochinvar Corporation, or your authorized sales representative, to report the damage and to receive instructions on how to proceed.

After the unit and all components have been inspected for damage, it is suggested that all pressure and temperature control components be checked to assure that they meet or exceed design specifications. If any discrepancy is found, contact Lochinvar Corporation, or your authorized representative, before proceeding with the installation.

Mounting the unit

The unit should be mounted to the floor, following applicable architectural / local code requirements, or accepted standards for the specific installation site. The unit should be installed in a location with sufficient

Connecting the cold water source and the hot water outlet

NOTICE

Before making any connections of water

inlet or outlet to the unit, assure that all

 

 

 

piping is clean and free of foreign material

 

or scale. This can usually be accomplished

 

by “blowing out” the pipe. Any foreign

 

material or scale entering the unit can

 

adversely

affect

operation

and

 

performance.

 

 

 

Cold water source

The first step in the installation process is to connect the cold water source to the water inlet port. The exact location of this port for the specific unit, as well as inlet pipe diameter and thread size, can be determined from the CAD drawing supplied with the unit.

A manual shutoff valve should be installed upstream on the cold water source as an isolation device. The shutoff valve should be in the closed position and remain so until the installation is complete.

clearance to remove the tube bundle for repair or replacement.

Unit and components

NOTICE

For all piping connections, the use and / or type of joint compound or sealer on the joint should be determined by referring to local codes, accepted practices, or the requirements of the installing contractor.

Lochinvar Hot Water Generators are designed to make installation a relatively simple procedure. Because the unit is “Packaged”, after placing and mounting the unit, installation involves the following:

Connecting the cold water source to the water inlet.

Connecting the hot water outlet to the hot water feed line.

Installing the control valve bulb into the tank bulbwell.

Connecting the condensate / water return line and piping it to the recycling system.

Piping the pressure relief valve to an acceptable drain.

Connecting the energy source (steam or boiler water) to the unit.

Wiring the applicable source of electricity (if the unit is packaged with a circulating pump or electrically activated pressure or temperature controls).

Each unit is supplied with CAD drawings that indicate the location and specifications for each connection that must be made. In addition, the drawing will enable the installer(s) to determine the flow direction of both the water and energy source.

If the cold water source is equipped with an in-line check valve or backflow preventer, a suitable expansion tank must be installed in the hot water outlet side of the system. See the supplied CAD drawing(s) or contact Lochinvar Corporation for expansion tank specifications.

Hot water outlet

The next step in the installation process is to connect the hot water system piping to the hot water outlet port. The exact location of this port for the specific unit, as well as outlet pipe diameter and thread size, can be determined from the CAD drawing(s) supplied with the unit.

A manual shutoff valve should be installed downstream on the hot water outlet line as an isolation device in case the unit must be disconnected from the system. The shutoff valve should be in the closed position and remain so until the installation is complete.

7

Page 7
Image 7
Lochinvar Hot Water Generator 2Installation continued, Examining the unit, Mounting the unit, Unit and components