Lochinvar SPS0250, SPS0500, PS1000 1 VFS 1-12flow ouput signal, 5 VFS flow sensor, Gnd Uv

Models: PS1000 SPS0500 SPS0250

1 16
Download 16 pages 20.75 Kb
Page 9
Image 9
6 VFS flow sensor

6 VFS flow sensor

Vortex flow sensor for liquid media.

Measures flow rate and temperature for BTU metering (energy balance, etc.)

Zero wear (no moving parts).

Figure 6-1VFS 1-12 flow ouput signal

VFS 1-12 output signal flow

Assignment of measurement range: 0.26-3.17 gpm is equal to 0.5-3.5V

Flow rate calculation: Q = 0.26gpm +[(U-0.5)V/3V]*2.91gpm

Figure 6-2VFS 1-12 temperature output signal

VFS 1-12 output signal temperature

Assignment of measurement range: 32-212° F is equal to 0.5-3.5V

Temperature rate calculation: T =32° F + [(U-0.5)V/3V]*180° F

SL-PS Installation & Operation Manual

Figure 6-4VFS 2-40 temperature output signal

VFS 2-40 output signal temperature

Assignment of measurement range: 32-212° F is equal to0.5-3.5V

Temperature rate calculation: T =32° F + [(U-0.5)V/3 V]*180° F

Figure 6-5VFS flow sensor

Item

Pin Configuration

1Temperature signal (0.5 to 3.5 relative to pin 3)
2Flow pressure signal (0.5 to 3.5 relative to pin 3)

3

GND (UV)

4

Voltage Supply (+5 VDC) PELV

Figure 6-3VFS 2-40 flow output signal

VFS 2-40 output signal flow

Assignment of measurement range: 0.53-10.6gpm is equal to 0.5-3.5V

Flow rate calculation: Q = 0.53gpm +[(U-0.5)V/3V]*10gpm

9

Page 9
Image 9
Lochinvar SPS0250, SPS0500 1 VFS 1-12flow ouput signal, 2 VFS 1-12temperature output signal, 5 VFS flow sensor, Gnd Uv